2-5
PRODUCT DATA SHEET
SM TQDCI 1-A.1 GB
2.3.5
K 12 DCI Specifications
Model Indoor Unit / Type
K 12 DCI / Cassette
Installation Method
FLARE
Power Supply
V/Ph/Hz
220-240 / 1/ 50
INDOOR
Fan Type & Quantity
Centifugal *1
Airflow
(2)
Cooling / Heating
H/M/L
m
3
/hr
580/620
510/560
435/450
Sound Power Level
(3)
Cooling / Heating
L - H
dB (A)
42-49 / 42-48
Sound Pressure Level
(4)
Cooling / Heating
L - H
dB (A)
32-38 / 32-38
Condensate Drain Tube I.D.
mm
16
Dimensions
W/H/D
mm
571
287
571
Weight
kg
24.4
Package Dimensions
W/H/D
mm
685
415
685
Stacking Height
Units
5
Heating Elements
kW
N/A
Moisture Removal
L/hr
1.5
2.3.6
K 18 DCI Specifications
Model Indoor Unit / Type
K 18 DCI / Cassette
Installation Method
FLARE
Power Supply
V/Ph/Hz
220-240 / 1/ 50
INDOOR
Fan Type & Quantity
Centifugal *1
Airflow
(2)
H/M/L
m
3
/hr
730
630
510
Sound Power Level
(3)
L - H
dB (A)
46 - 59
Sound Pressure Level
(4)
L - H
dB (A)
36 – 48.5
Condensate Drain Tube I.D.
mm
16
Dimensions
W/H/D
mm
571
287
571
Weight
kg
28
Package Dimensions
W/H/D
mm
685
415
685
Stacking Height
Units
5
Heating Elements
kW
N/A
Moisture Removal
L/hr
2
NOTE
1) Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units) and EN14511.
(2) Airflow in ducted units; at nominal external static pressure.
(3) Sound power in ducted units is measured at air discharge.
(4) Sound pressure level measured at 1 meter distance from unit.
:
CONTENTS