15
Use a pozidrive m3.5 screwdriver, Form Z, to make the connections.
These units are equipped with a local switch used as general terminal board.
The proximity switch can be mounted at two different locations:
The switch can be padlocked.
A circuit breaker or fuse holder ( not supplied ) must be installed on the main power
supply of the unit in accordance with the circuit diagram; for the raitings, refer to the
electrical specifications.
3N~400v
CONNECTION OF RCW2 AND REMOTE ROOM TEMpERATURE
100 m mAXI
1 mm² mAXI
Shielded cable
RS485
GND
12v
12V
GND
1
2
RT
GND
IF the RT sensor is not used, the RCW2 must be configured in Zone 1 with the local temperature function
activated.
Remote room temperature
sensor delivred with
the machine (optional
installation)
1000 m mAXI
Shielded 2 twisted pairs cable
with setting with terminal GND.
0,12 à 0,3 mm²