Connect the pipe of the airline support assembly on the existing poly
end connector as indicated.
Mount the airline support assembly in place by bolting it through the
existing float holes with the use of:
-
2 x securing plates M1104
-
2 x threaded rods M718B[002]
-
4 x washers H688
-
4 x nuts H697
At each end of the cable kit, there is a plastic plug. It is important to
ensure the two O-rings fitted into the grooves of the plug with the
stainless-steel nut, are clean and in good condition.
Do not use any sealer on these plugs, although generous amounts of
penetrating oil / water dispersant are recommended to lubricate O-
rings.
Note: If water has entered the cable kit, the pump will not
operate. Contact Airwell for drying and repair instructions.
Attach the cable kit plug with the stainless-steel nut into the probe
as indicated. This plug will only plug into the probe one way.
Push the cable kit plug with the stainless-steel nut on the top of the
probe holder, as far as you can into the socket.
Screw the nut,
ensuring you don’t use it to drive the plug home, as it
may be inclined to strip the thread.
The nut should only be finger tight.
Note: Damage to the O-rings and plastic parts could result from
over
–
tightening.
Connect the airline to the existing poly joiner as indicated.