Unit:mm
Required tools for installation works
NO.
Tool
NO.
Tool
NO.
Tool
1
Screw driver
5
Pipe cutter
9
Torque wrench
18 Nm (1.8 kgf.m)
45 Nm (4.5 kgf.m)
65 Nm (6.5 kgf.m)
75 Nm (7.5 kgf.m)
2
Electric drill, hole core
drill ( 60 mm)
6
Reamer
3
Hexagonal wrench
7
Knife
4
Spanner
8
Measuring tape
Attached accessories
No.
Accessories part
Qty.
No.
Accessories part
Qty.
No.
Accessories part
Qty.
1
Central control
display (optional)
1
3
Drain tube+clips
1
5
Unit operation manual
Installation manual
2
2
Tie-Waps
6
4
Screws washer
dowels
5
6
Gas tubing insulation
1
1
SELECT THE BEST LOCATION
While selecting a place for the indoor unit
Allow max. air flow to the desire space.
Allow max return air flow.
Ensure adequate drainage of condensed water.
T
he distance between air-conditioner and obstacles should meets the requirments in below fig.
Leave a minimum 250 mm free space in front of the filter.
Allow a free service access to electrical box.
Allow easy access to the base of the indoor unit while providing enough space from the ceiling.
The installation height should over 2.3m.
2
UNIT INSTALLATION
1.HOLES DRILLING LOCATION ON THE CEILING FOR INDOOR UNIT
Model
A
B
DLV007-DLV015
790
565
DLV018-DLV024
1090
565
2.DRAINAGE INSTALLATION
General
For an efficient functioning of the drainage system, please take care of the following:
Always balance the unit with 2 downward to the drainage side of the unit.
●
Use 19 mm tube drainage.
●
It is recommended to prepare a drainage point by professional plumber close to the unit.
●
For proper drainage, the passage must be planned with 1 down slope.
●
Prevent any upwards or reverse flow in any part.
●
For preventing of unpleasant smells in the room, install a siphon in the installation. Install the draining tube with 6 mm thickness t
●
hermal insulation sleeve.