28
continuously, till stop cooling or dry or no capacity
demand.
2. Once the water level increase and up to the
control point, LED will alarm and the drain pump
open and continue checking the water level. If the
water level falls down below the control point (drain
pump delay close 1 minute) and operate with the
last mode. Otherwise the entire system stop
operating (including the pump) and LED remain
alarming after 3 minutes,
8.4.11 Follow me (optional)
1) If the indoor PCB receives the signal which
results from pressing the FOLLOW ME button
on remote controller, the buzzer will emit a
sound and this indicates the follow me function
is initiated. But when the indoor PCB receives
signal which sent from remote controller every
3 minutes, the buzzer will not respond. When
the unit is running with follow-me function, the
PCB will control the unit according to the
temperature from follow-me signal, and the
temperature collection function of room
temperature sensor will be shielded, and the
error detective function of room temperature
sensor will be still invalid.
2) When the follow-me function is available, the
PCB will not respond according to the setting
temperature from follow-me signal every 3
minutes.
3) The PCB will take action to the mode change
information from remote controller signal, and
the follow-me function will be turned off. (if the
wired remote controller does not initiate follow
me function).
4) When the unit is running with follow-me
function, if the PCB doesn’t receive any signal
from remote controller for 7 minutes or
pressing FOLLOW ME button again, the
follow-me function will be turned off
automatically, and the temperature collection
function of room temperature sensor will be
available, the PCB will control the unit
according to the room temperature detected
from its own room temperature sensor and
setting temperature.
5) When the indoor PCB receives the follow-me
signal from wired remote controller, the control
is the same as that from wireless remote
controller, but buzzer will not emit a sound.
When the PCB receives turning-off follow-me
signal from wired remote controller, the unit will
quit follow-me function at once. The follow-me
function controlled by wired remote controller
prevails that by wireless remote controller.
8.4.12 Mode conflict
The indoor units cannot work cooling mode and
heating at same time.
Heating mode has a priority.
(1) Definition
Cooling
mode
Heating
Mode
Fan
Off
Cooling
mode
No
Yes
No
No
Heating
Mode
Yes
No
Yes
No
Fan
No
Yes
No
No
Off
No
No
No
No
No: No mode conflict;
Yes: Mode conflict
(2) Unit action
In case of one Indoor unit working in cooling
mode or fan mode, and another indoor unit is
set to heating mode, the indoor unit working
in cooling mode or fan mode will change to off.
The outdoor unit will change to heating mode
after compressor stop 3 minutes. .
In case of one Indoor unit working in heating
mode, and another indoor unit is set to
cooling mode or fan mode, the indoor unit
setting to cooling mode or fan mode will
change to stand by. The outdoor unit will
Summary of Contents for CDMX-022N-09M25
Page 12: ...10 3 4 New console XDMX...
Page 15: ...13 5 Wiring diagram CDMX 025N 09M25...
Page 16: ...14 CDMX 035N 09M25 CDMX 050N 09M25 CDMX 070N 09M25...
Page 17: ...15 DDMX 022N 09M25 DDMX 035N 09M25 DDMX 050N 09M25 DDMX 070N 09M25...
Page 18: ...16 XDMX 035N 09M25 XDMX 050N 09M25...
Page 20: ...18 DDMX 035N 09M25...
Page 21: ...19...
Page 22: ...20 DDMX 050N 09M25...