11-8
CONTROL SYSTEM
SM BS DCI 1- A.1 GB
Control Status
Compressor Temperature
Increases
Else
P1 Norm SR
P2 D1 SR
P3 D2 D1
Stop Compressor
SC
11.19.4
Compressor over Current Protection
Normal
Stop-Rise
HzDown1
HzDown2
Stop-Compresor
CCROC1
CCROC2
CCROC3
CCROC4
CCR
11.19.5
Heat Sink over Heating Protection (NA for DCI 25 and 35
HST Trend
HST
Decreasing
No Change
Increasing
HST
>
90
SC SC SC
85 < HST 90
D1
D2
D2
82 < HST 85
SR
D1
D2
80 < HST 82
SR
SR
D1
78 < HST 80
Norm
Norm
SR
HST 78
Normal
CONTENTS