background image

 

 

 
 
 

 

 

 

 

 

 

 
 

 

INDOR UNIT 

OUTDOR UNIT 

Type 

Image 

Model 

Model 

   
  
Floor Ceiling

 

 

 

 

 
FAF 060 

– N11 

 
                         AWSI YIFA060

–H13 

 

 

 

 

 

 

 

 

 

 

  

 

 

R410A 

HEAT PUMP 

MAY 2013 

SM FAF 060 – 1-A. 1GB 

Version : 1 

Summary of Contents for AWSI YIFA060-H13

Page 1: ...INDOR UNIT OUTDOR UNIT Type Image Model Model Floor Ceiling FAF 060 N11 AWSI YIFA060 H13 R410A HEAT PUMP MAY 2013 SM FAF 060 1 A 1GB Version 1 ...

Page 2: ...ODUCT DATA SHEET 3 3 RATING CONDITIONS 5 4 OUTLINE DIMENSIONS 6 5 PERFORMANCE DATA 7 6 ELECTRICAL DATA 8 7 WIRING DIAGRAMS ELECTRICAL CONNECTIONS 11 8 REFRIGERATION DIAGRAMS 13 9 TUBING CONNECTIONS 14 10 CONTROL SYSTEM 15 11 TROUBLESHOOTING 25 12 EXPLODED VIEWS AND SPARE PARTS LISTS 54 ...

Page 3: ... efficiency and no condensation on shell Long term air filter the wash period is two times longer than normal filter maintenance is free Adopting low noise centrifugal fan strong wind but quiet operation the silence design achieves harmony residential living All the installation and maintenance can be done in the bottom of unit saving the maintenance space 3 phase power supply type units with low ...

Page 4: ...1 6 d Fin Material Hydrophilic aluminum fin e Tube Outside Dia and Material mm φ9 52 Inner grooved f Coil Length x Height x Width mm 1333 220 38 1 g Heat Exchanging Area m2 16 36 Indoor Unit Indoor Air Flow Hi Mi Lo m3 h 1800 1440 1260 Noise Level Hi Mi Lo dB A 51 48 42 External Static Pressure Pa 0 Net Dimension W H D mm 1631 660 205 Packing Dimension W H D mm 1710 720 280 Net Weight Kg 44 Gross ...

Page 5: ...2 b Tube Pitch a x Row Pitch b mm 22 19 05 c Fin Pitch mm 1 6 d Fin Material Hydrophilic aluminum fin e Tube Outside Dia And Material mm φ7 94 Inner grooved f Coil Length x Height x Width mm 750 1188 38 1 g Heat Exchanging Area 38 85 Air Flow Volume CFM 3059 m3 h 5200 Noise Level dB A 62 Dimension W D H Net mm 945 340 1255 Packing mm 1090 430 1370 Weight Net kg 101 Gross kg 115 Refrigerant Type Qu...

Page 6: ...v i c e M a n u a l RATING ONDITIONS 3 RATING CONDITIONS 3 1 Rating Conditions Power supply 380 415V 3N 50Hz Voltage 320 420V Outdoor ambient temperature Cooling 5 49 Low ambient cooling function Heating 10 24 ...

Page 7: ...6 S e r v i c e M a n u a l OUTLINE DIMENSIONS 4 OUTLINE DIMENSIONS 4 1 FAF 060 N11 4 2 YIFA 060 H13 ...

Page 8: ...ominal cooling capacity could be found from the performance parameters list Amendment coefficient of cooling capacity could be found from table above 5 2 Amendment coefficient of heating capacity under different indoor outdoor DB and WB temperature Indoor air inlet DB temperature Outdoor air inlet WB temperature 5 0 6 10 15 16 0 65 0 80 1 02 1 13 18 0 61 0 76 1 02 1 12 20 0 6 0 75 1 1 11 1 25 21 0...

Page 9: ...d cooling capacity under different height drop Different Cooling Capacity modified coefficients at different height Note H Height of Outdoor Unit Height of Indoor Unit Different Heating Capacity modified coefficients at different height Note H Height of Outdoor Unit Height of Indoor Unit ...

Page 10: ...5 88 Φ19 05 Max Length m Liquid Pipe Dia Φ6 35 Φ9 52 Φ9 52 Gas Pipe Dia Φ12 7 Φ15 88 Φ19 05 Max Length 20 30 50 Max Height m 15 15 30 Max Bend Qty 4 4 10 Extra R410a per meter when the pipe length is more than 5 meter kg 0 02 0 02 0 07 Caution 1 The standard Pipe length is 5m if the pipe length is less than this then no additional charging is necessary If the pipe length is more than this then you...

Page 11: ... and outdoor unit it is F3 15AL 250V Machine must be earthed surely If not it ll be probably caused creepage Equivalent 227IEC53 RVV type of power cord of GB5023 or the excelled must be required The cords should be fixed properly against broken while ends joints of cords is under outside force Improper connection or fixation will cause disaster like fire etc Equivalent 245IEC57 YZW type of power c...

Page 12: ...unit is the power supply cable connecting indoor and outdoor unit The section area of power supply cord core is minimized one To avoid voltage pressure dropped down while longer power supply cord needed the section area should be enlarged for one gauge The connection wires to indoor unit is the cable of 27IEC53 RVV type 300 500V while the connection wires to outdoor unit and the connection wires f...

Page 13: ...connect the wires in accordance with the electric diagram on the back of the cover Be sure that pressing the wires tightly with the terminal boards while it through the board the wire ends must be tightly fixed into terminal boards The earth wire must be fixed into appointed position After all the wire connected bundle connection pipe connection wires and drainage pipe with strips like mentioned d...

Page 14: ...13 S e r v i c e M a n u a l WIRING DIAGRAMS ELECTRICAL CONNECTIONS 7 WIRING DIAGRAMS ELECTRICAL CONNECTIONS 7 1 FAF 060 N11 ...

Page 15: ...14 S e r v i c e M a n u a l WIRING DIAGRAMS ELECTRICAL CONNECTIONS 7 2 YIFA 060 H13 7 3 Indoor Unit FAF 060 N11 Outdoor Unit YIFA 060 H13 ...

Page 16: ...15 S e r v i c e M a n u a l REFRIGERATION DIAGRAMS 8 REFRIGERATION DIAGRAMS 8 1 Indoor Unit FAF 060 N11 Outdoor Unit YIFA 060 H13 ...

Page 17: ...16 S e r v i c e M a n u a l 9 TUBING CONNECTIONS TUBING CONNECTIONS ...

Page 18: ...or unit runs at low wind for 20 seconds while other equipment not start after 20 seconds indoor fan stops the units enters into mode judgment b Once the room temperature over 27 the units run in cooling mode of setting wind and setting temperature 24 c When the room temperature is between 20 and 27 the units run in dehumidifying mode of setting wind and setting temperature 24 d When the room tempe...

Page 19: ...temperature button on remote controller or wired controller Press fan speed button to choose fan speed among auto wind high speed wind medium speed wind low speed wind Operation state a When TA TS 2 and 3 min protection can be satisfied the compressor and outdoor fan will run continuously and wind speed run at set speed b When TS TA TS 2 and 3 min protection can be satisfied the compressor and out...

Page 20: ...e set at high medium low by remote controller Heating operation Temperature is set by remote controller or wired controller temperature control range from 16 32 user can adjust temperature through temperature and temperature button on remote controller or wired controller Press fan speed button to choose fan speed among auto wind high speed wind medium speed wind low speed wind Operation state a W...

Page 21: ...h set temperature or turn off the unit if TE 35 indoor fan motor operates at low wind if indoor temperature 35 indoor fan stops running Swing control There are totally 4 swing modes A B C D among them A and B is an assembly C and D is an assembly Each mode switches through sleep button on remote control or wired control detail operation is as follows press sleep button 10 times continuously in 5 s...

Page 22: ...e set temperature raises by 1 1 h later and for heating operation the set temperature descends by 2 1 h later After another 1h operation for cooling operation the set temperature raises by 1 again and for heating operation the set temperature descends by 2 again After the sleeping mode runs for 7h the unit shutdown When enters into sleeping operation mode switch will be valid however sleeping func...

Page 23: ...ads to compressor exhaust pressure over using range to cause compressor damage b When outdoor coil temperature 64 and lasts for over 20s the compressor stops running when the coil temperature 52 degree and the 3 min compressor protection is satisfied the compressor returns to normal running c Once high pressure protection appears 3 times in half an hour the whole unit stops running and indoor unit...

Page 24: ...utdoor unit appears lack phase or phase sequence incorrect the unit stops immediately and enters into protection alarming outdoor protection even phase sequence or lack phase switch return to normal the failure code will not disappear the unit can resume when restarting Outdoor fan motor control The unit has function of low ambient cooling and high ambient heating when cooling take outdoor coil te...

Page 25: ...As for secondary condition in upper condition it is only valid that all secondary condition be satisfied at the same time a Condition No 1 The outdoor fan enters into over load protection and stops running Outdoor fan stops running then restarts and keeps running over 10 min The compressor accumulating running time 45min The compressor continuous running time 20min TE 48 b Condition No 2 Enter int...

Page 26: ... compare current TE with TE before defrosting if the latter doesn t high than former by 3 or more next time unit will not enter into defrosting at this condition until mode switch turn off then restart to heating or go through a defrosting yet e Condition No 5 Begin to calculate time once air conditioner enters into over heating protection enters into compulsory defrosting after 2 h later f Condit...

Page 27: ...ll be checked if TW is abnormal unit normal starting is permitted and defrosting automatically be set as intelligent failure code will display see the failure indication table failure code disappears when TW return to normal and heating defrosting returns to normal d Exhaust temperature TP Check the exhaust temperature sensor when power on When TP is abnormal unit will start normally and exhaust o...

Page 28: ...v i c e M a n u a l 11 TRUBLESHOOTING TRUBLESHOOTING 11 1 Failure Code When air condition has failure the timing lamp on light board of controller will display different code according to different failure case ...

Page 29: ...otection Flash 9 times and go out 2S Flash 1 times and go out 2S E9 6 shutdown Low pressure protection Flash 9 times and go out 2S Flash 3 times and go out 2S E9 6 shutdown Indoor temp sensor abnormal TA Flash 1 times and go out 2S E1 4 shutdown Indoor coil sensor abnormal TE Flash 3 times and go out 2S E3 5 shutdown Outdoor coil sensor abnormal TW Flash 2 times and go out 2S Flash 2 times and go ...

Page 30: ...29 S e r v i c e M a n u a l TRUBLESHOOTING 11 3 Failure analysis and elimination 11 3 1 Analysis and elimination for the failure with failure code ...

Page 31: ...30 S e r v i c e M a n u a l TRUBLESHOOTING Communication failure between indoor and outdoor unit ...

Page 32: ...31 S e r v i c e M a n u a l TRUBLESHOOTING Drainage system failure ...

Page 33: ...32 S e r v i c e M a n u a l TRUBLESHOOTING Outdoor protection phase sequence ...

Page 34: ...33 S e r v i c e M a n u a l TRUBLESHOOTING Cooling high pressure protection ...

Page 35: ...34 S e r v i c e M a n u a l TRUBLESHOOTING Heating high pressure protection ...

Page 36: ...35 S e r v i c e M a n u a l TRUBLESHOOTING Cooling low pressure protection ...

Page 37: ...36 S e r v i c e M a n u a l TRUBLESHOOTING Heating low pressure protection ...

Page 38: ...37 S e r v i c e M a n u a l TRUBLESHOOTING Cooling exhaust temperature protection ...

Page 39: ...38 S e r v i c e M a n u a l TRUBLESHOOTING Heating exhaust temperature protection ...

Page 40: ...39 S e r v i c e M a n u a l TRUBLESHOOTING Refrigerant shortage or four way valve failure protection ...

Page 41: ...40 S e r v i c e M a n u a l TRUBLESHOOTING Sensor failure protection ...

Page 42: ...41 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 Analysis and elimination for the failure without failure code 11 4 1 No action after power on ...

Page 43: ...42 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 2 Air conditioner operates but effect is terrible ...

Page 44: ...43 S e r v i c e M a n u a l TRUBLESHOOTING ...

Page 45: ...44 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 3 Abnormal sound or vibration ...

Page 46: ...45 S e r v i c e M a n u a l TRUBLESHOOTING ...

Page 47: ...46 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 4 Abnormal odor ...

Page 48: ...47 S e r v i c e M a n u a l TRUBLESHOOTING 11 4 5 Air switch action when air conditioner starting up ...

Page 49: ... too many indoor individuals even air conditioner runs at full load operation the wind blowing out from air outlet is cold but it is difficult to lower the indoor temperature this is not malfunction When the outdoor temperature is higher more heat penetrates into indoor space which increases the cooling load of AC If there are too many individuals for example 10 individuals and every individual gi...

Page 50: ... effect is not ideal during cold winter this is normal phenomenon The lowest temperature is 7 when heating below this temperature unit cannot heat effectively Improper installation will lead to indoortemperature uneven or bad cooling effect It is necessary to adjust AC installation position 11 5 2 It means there is failure if following phenomenon is happened Phenomenon Causing explanation Mirage c...

Page 51: ...nt of contactor has no burn and melt phenomenon 3 The winding has resistance value below 1000 but cannot be nil or infinite 4 4 ways valve winding The winding has resistance value below 1000 but cannot be nil or infinite 5 Capacitor 1 No expansion phenomenon apparently 2 Measure capacitor by using capacitor phase of multi meter if the multi meter has no capacitor phase use ohm phase contact the tw...

Page 52: ...5 72 1 013 8 20 56 33 3 695 73 0 9837 7 19 61 34 3 562 74 0 9550 6 18 72 35 3 434 75 0 9273 5 17 87 72 3 311 76 0 9005 4 17 06 37 3 193 77 0 8746 3 16 30 38 3 081 78 0 8496 2 15 57 39 2 972 79 0 8254 1 14 88 40 2 869 80 0 8021 0 14 23 41 2 769 81 0 779 1 13 60 42 2 673 82 0 758 2 13 01 43 2 581 83 0 737 3 12 45 44 2 493 84 0 716 4 11 91 45 2 409 85 0 696 5 11 40 46 2 307 86 0 677 6 10 92 47 2 249 ...

Page 53: ...77 6 914 117 2 083 2 170 7 38 28 23 78 6 693 118 2 026 1 162 4 39 27 13 79 6 480 119 1 972 0 154 5 40 26 07 80 6 276 120 1 920 1 147 1 41 25 06 81 6 075 121 1 868 2 140 0 42 24 09 82 5 881 122 1 819 3 133 3 43 23 17 83 5 694 123 1 772 4 127 1 44 22 29 84 5 514 124 1 725 5 121 1 45 21 44 85 5 340 125 1 680 6 115 4 46 20 64 86 5 175 126 1 636 7 109 9 47 19 86 87 5 014 127 1 594 8 104 9 48 19 13 88 4...

Page 54: ...1 5 Left side adornment plank A16420015000002 1 6 The electricity controls a box A16421038000009 1 7 The electricity controls a box of cover A16421005000205 1 8 Compress tightly electric wire seat A11220544000008 1 Compress tightly electric wire cover A11220544000008 1 9 Terminal board A16427001000003 1 10 Transformer A16422005000017 1 11 Capacitor A16430015000005 1 12 PCB board A16422001000029 1 ...

Page 55: ...00022 1 27 Connect a pole A16420008000003 1 Connect a pole A16420008000005 1 28 Perpendicular blade A16420007000008 1 29 Right foam A16428001000018 1 30 Bracket board welding assembly of right hand A16321006000006 1 31 Right suspend plate A16421001000030 1 32 The Right side covers A16420014000008 1 33 Draining tray A16321006000007 1 34 Drain pipe A16432019000004 1 35 Volute fixing board A164210020...

Page 56: ...5004000814 1 12 1 Low Pressure Switch A16442024000005 1 13 Oil heat strap A16430022000002 1 14 Four way valve assembly A16325004000815 1 14 1 High Pressure Switch A16442024000010 1 14 2 Four way valve A11225509000067 1 14 3 Four way valve loop A11330011000030 1 14 4 Muffler A16325004000796 1 15 Right hand board A11321007000088 1 16 valve plate A11321031000016 1 16 1 Stop valve 3 8in A1644100400005...

Page 57: ......