![Airwell AWSI-HBV007-N11 Service Manual Download Page 13](http://html1.mh-extra.com/html/airwell/awsi-hbv007-n11/awsi-hbv007-n11_service-manual_2880027013.webp)
11
6.
Electric characteristics
Units
Power supply Indoor fan motor Power input (W)
Model
Phase
FQY
Voltage
Volt.
range
MCA
MFA Output
(W)
FLA
Cooling
Heating
AWSI-HBV007-N11
1
50/60
220
198~242 0.18
0.56
30
0.14
43
43
AWSI-HBV009-N11
1
50/60
220
198~242 0.18
0.56
30
0.14
43
43
AWSI-HBV012-N11
1
50/60
220
198~242 0.18
0.56
30
0.14
43
43
AWSI-HBV016-N11
1
50/60
220
198~242 0.24
0.76
40
0.19
57
57
AWSI-HBV018-N11
1
50/60
220
198~242 0.24
0.76
40
0.19
57
57
AWSI-HBV024-N11
1
50/60
220
198~242 0.24
0.76
40
0.19
57
57
AWSI-HBV030-N11
1
50/60
220
198~242
0.4
1.28
70
0.32
99
99
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Notes:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA.
4. Power supply uses the circuit breaker.