12-10
SM HDDE 1-A.1 GB
limitation and prevent abnormal high pressure.
CONTROL SYSTEMS
For Model 09/12: Compressor will stop when ICT reaches 62C
For Model 18/24, Compressor will stop when ICT reaches 64C
If the unit stops as such protection for 6 times, it can not resume running automatically and display
the error code
E8
, it can resume by pressing ON/OFF.
During the operating, If compressor operates for more than 10min, the counter of stop operation
due to protection will be cleared.
12.11.4
Outdoor Coil Overheating protection (Cool/Dry Mode):
During heating operation, the ODU Coil Overheating Protection is detected by temperature sensor
OCT.
For Model 09/12: Compressor will stop when OCT reaches 62C
For Model 18/24, Compressor will stop when OCT reaches 65C
If the unit stops as such protection for 6 times, it can not resume running automatically and display
the error code
E8
, it can resume by pressing ON/OFF.
During the operating, If compressor operates for more than 10min, the counter of stop operation
due to protection will be cleared.
12.11.5
Compressor over Current Protection
Detect an input current by the CT during the compressor is running, and set the frequency upper
limit from such input current. In case of heat pump model, this control is the upper limit control
function of the frequency which takes priority of the lower limit of four way valve activating
compensation.
Detail
Model 09/12: Compressor will stop when AC current reaches 14.0A for continuously 2.5s.
Model 18/24: Compressor will stop when AC current reaches 17.0A for continuously 2.5s.
If the unit stops as such protection for 6 times, it can not resume running automatically and display
error Code
E5
, it can resume by pressing ON/OFF.
During the operating, If compressor operates for more than 10min, the counter of stop operation
due to protection will be cleared.
12.11.6
Outdoor Coil Deicing Protection
This protection is for Heat Pump Only
This protection is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor
heat exchanger temperature must be more than its setting values when finishing the deicing
protection.
In the deicing protection, IFAN is forced OFF.
Summary of Contents for AWAU-YDDE009-H11
Page 14: ...OUTLINE DIMENSION SM HDDE 1 A 1 GB 4 2 4 2 Outdoor YDDE009 4 3 Outdoor YDDE012...
Page 15: ...4 3 SM HDDE 1 A 1 GB SOUND LEVEL CHARACTERISTICS 4 4 Outdoor YDDE018 4 5 Outdoor YDDE024...
Page 16: ...PERFORMANCE DATA SM HDDE 1 A 1 GB 5 1 5 PERFORMANCE DATA...
Page 17: ...SOUND LEVEL CHARACTERISTICS SM HDDE 1 A 1 GB 6 1 6 PRESSURE CURVES...
Page 21: ...SM HDDE 1 A 1 GB 9 1 WIRING DIAGRAM 9 WIRING DIAGRAM 9 1 HDDE009 HDDE012 9 2 HDDE018...
Page 22: ...WIRING DIAGRAM SM HDDE 1 A 1 GB 9 2 9 3 HDDE024 9 4 YDDE009...
Page 23: ...9 3 SM HDDE 1 A 1 GB WIRING DIAGRAM 9 5 YDDE012 9 6 YDDE018 YDDE024...
Page 40: ...12 15 SM HDDE 1 A 1 GB 12 14 Test Mode TO BE CONFIRMED...
Page 47: ...14 2 SM HDDE 1 A 1 GB CHARACTERISTICS OF SENSOR 14 1 3 CTT CTT R T Chart...
Page 51: ...EXPLODED VIEW SPARE PART LIST 15 4 SM HDDE 1 A 1 GB 15 4 Exploded view of indoor unit HDDE018...
Page 58: ...SM HDDE 1 A 1 GB 15 11 SERVICING 15 11 Exploded view of outdoor unit YDDE018...
Page 60: ...SM HDDE 1 A 1 GB 15 13 SERVICING 15 13 Exploded view of outdoor unit YDDE024...
Page 63: ...SM HDDE 1 A 1 GB a APENDIX APPENDIX...
Page 64: ...SM HDDE 1 A 1 GB 15 15 SERVICE MANUAL HDDE009 012 018 024...