Electric wiring and the application
3RZHUZLULQJ¿JXUH
Outdoor power source and power cable
3OHDVHPDNHVXUHWKDWZKHQWKHXQLWLVUXQQLQJWKHLQSXWYROWDJHLVQROHVVWKDQ9
if it is lower than 380V,the unit may run abnormal.
,QGRRUDQGRXWGRRUXVHWKHLULQGLYLGXDOSRZHUVRXUFH
All indoors use one power source.
0XVWLQVWDOOWKHOHDNDJHEUHDNHUDQGWKHRYHUFXUUHQWEUHDNHURUHOHFWULFVKRFNZLOORFFXU
3RZHUFDEOHPXVWEH¿[HG¿UPO\
Each outdoor must be earthed well.
When power cable exceeds the range, thicken it appropriately.
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
power source: 3N~, 380-400V, 50/60Hz
Item
Model
Power
source
Power
cable
section
(mm
2
Wire
length
P
Circuit
breaker
$
Rated current of residual
FLUFXLWEUHDNHU$
Ground fault
LQWHUUXSWRUP$
UHVSRQVHWLPH6
Ground wire
Section
(mm
2
Screw
,Q
GL
YL
GX
DO
S
RZ
HU
YCVFD224
3N~,
380-
400V,
50/60
Hz
6
60
40
40A 30mA below 0.1S
3.5
M5
YCVFD280
10
60
40
40A 30mA below 0.1S
3.5
M5
YCVFD335
10
60
40
40A 30mA below 0.1S
3.5
M5