PRODUCT DATA SHEET
SM FWDE 1-A.1 GB
2-1
2.
PRODUCT DATA SHEET
2.1
AWSI-FWDE012-N11// AWAU-YBDE012-H11
Model Indoor Unit
AWSI-FWDE012-N11
Model Outdoor Unit
AWAU-YBDE012-H11
Installation Method of Pipe
Flared
Characteristics
Units
Cooling
Heating
Btu/hr
11940(5120~15010)
-
Capacity (4)
kW
3.5(1.5~4.4)
-
Pdesign(5)
kW
3.5
-
Power input (4)
kW
0.98
-
EER (Cooling) or COP(Heating) (4)
W/W
3.57
-
Energy efficiency class
A
-
SEER/Energy Label
5.3/A
-
Power supply
V/Ph/Hz
230V/Single/50Hz
Rated current
A
4.4
-
Starting current
A
10.5
Circuit breaker rating
A
16
Fan type & quantity
Centrifugal x 2
Fan speeds
H/M/L
RPM
830/760/500
Air flow (1)
H/M/L
m3/hr
450/400/300
External static pressure
Min-Max
Pa
0
Sound power level (2)
H/M/L
dB(A)
56/53/51
Sound pressure level(3)
H/M/L
dB(A)
45/41/30
Moisture removal
l/hr
1.5
Condenstate drain tube I.D
mm
16
Dimensions
WxDxH
mm
820x190x630
Weight
kg
22
Package dimensions
WxDxH
mm
890x280x710
Package weight
kg
26
Units per pallet
units
14
IN
D
O
O
R
Units stacking
units
7 levels
Refrigerant control
EEV
Compressor type,model
Single Rotary,DC Inverter,Panasonic 5RS102XAB
Fan type & quantity
Propeller(direct) x 1
Fan speeds
H/L
RPM
830
Air flow
H/L
m3/hr
1780
Sound power level
H/L
dB(A)
62
Sound pressure level(3)
H/L
dB(A)
52
Dimensions
WxDxH
mm
790x290x610
Weight
kg
38.5
Package dimensions
WxDxH
mm
970x394x650
Packaged weight
kg
42.5
Units per pallet
units
12
Stacking height
units
3 levels
Refrigerant type
R410A
Refrigerant charge
kg
1.2
Additional charge per 1 meter
g/m
No Need
Liquid line
In.(mm)
1/4"(6.35)
Suction line
In.(mm)
3/8"(9.53)
Max.tubing length
m.
Max.20
O
U
T
D
O
O
R
Connections
between units
Max.height difference
m.
Max.10
Operation control type
Remote control
Heating elements (Option)
kW
Others
(1)Airflow in ducted units;at nominal external static pressure.
(2)Sound power in ducted units is measured at air discharge.
(3)Sound pressure level measured at 1-meter distance from unit.
(4)Rating conditions in accordance to ISO 5151 and ISO 13253 (for ducted units).
(5)According to EN14825-2012
Summary of Contents for AWAU-YBDE012-H11
Page 10: ......
Page 11: ...OUTLINE DIMENSIONS SM FWD 1 A 1 GB 3 1 3 OUTLINE DIMENSIONS 3 1 FWDE012 3 2 FWDE018 024...
Page 12: ...OUTLINE DIMENSIONS 3 2 SM FWD 1 A 1 GB 3 3 Outdoor Unit YBDE 012 018 3 4 Outdoor Unit YBD 024...
Page 13: ...WIRING DIAGRAMS SM FWDE 1 A 1 GB 4 1 4 WIRING DIAGRAMS 4 1 Indoor Unit FWDE012 018...
Page 14: ...WIRING DIAGRAMS 4 2 SM FWDE 1 A 1 GB 4 2 Outdoor Unit YBDE012...
Page 15: ...WIRING DIAGRAMS SM FWDE 1 A 1 GB 4 3 4 3 Outdoor Unit YBDE018...
Page 16: ......
Page 17: ...WIRING DIAGRAMS SM FWDE 1 A 1 GB 4 1 4 4 Indoor Unit FWDE024...
Page 18: ...WIRING DIAGRAMS 4 2 SM FWDE 1 A 1 GB 4 5 Outdoor Unit YBDE024...
Page 20: ......
Page 23: ...EXPLODED VIEWS SPARE PART LISTS SM FWDE 1 A 1 GB 6 3 6 3 Exploded view of Indoor unit FWDE018...
Page 25: ...EXPLODED VIEWS SPARE PART LISTS SM FWDE 1 A 1 GB 6 5 6 5 Exploded view of Indoor unit FWDE024...
Page 27: ...EXPLODED VIEWS SPARE PART LISTS SM FWDE 1 A 1 GB 6 7 6 7 Exploded view of outdoor unit YBDE012...
Page 29: ...EXPLODED VIEWS SPARE PART LISTS SM FWDE 1 A 1 GB 6 9 6 9 Exploded view of outdoor unit YBDE018...