Functions and control
19
Domestic air conditioner
(18K/24K)
TC(
ć
)
The compressor stops
Fgh_t1 63
ć
/63
ć
Fgh_t1
ˉ
2
Fgh_t2
ˉ
2
N Decreasing the frequency rapidly Fgh_t2 59
ć
/59
ć
P Decreasing the frequency slowly Fgh_t3 56
ć
/57
ć
Fgh_t3
ˉ
2
Fgh_t4—2
Q Prohibiting increasing the frequency Fgh_t4 53
ć
/51
ć
R Increasing slowly
Fgh_t5 40
ć
/40
ć
Fgh_t5—2
Normal
N
˖
Decreasing at the speed of 1HZ/1 second
P
˖
Decreasing at the speed of 1Hz/10 seconds
Q
˖
Continue to keep the last-time instruction cycle
R
˖
Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
7.1.5.3 The control of preventing the over current of the compressor:
ƽ
During the starting process of the compressor, if the current of the compressor is greater than 15.5A
/17A(18K/24K)for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such
state appears 3 times in 20 minutes, stop the compressor and alarm, and confirm the malfunction.
Then continue to run it only after the power is off.
ƽ
During the starting process of the compressor, if the AC current is greater than 14.5A/15A(18K/24K),
the frequency of the compressor decreases at the speed of 1HZ/second.
ƽ
During the starting process of the compressor, if the AC current is greater than 13.5A/14A(18K/24K),
the frequency of the compressor decreases at the speed of 0.1HZ/second.
ƽ
During the starting process of the compressor, if the AC current is greater than 13A/13A(18K/24K),
the frequency of the compressor increases at the prohibited speed.
ƽ
During the starting process of the compressor, if the AC current is greater than 11.5A/12A(18K/24K)
the frequency of the compressor increases at the speed of no faster than 0.1HZ/second.
7.1.5.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 15.5A/17.5A(18K/24K)
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the the power is off.
During the starting process of the compressor, if the AC current is greater than 14.5A 15A(18K/24K),
the frequency of the compressor decreases at the speed of 1HZ/second.
Summary of Contents for AW-YHDM018-H91
Page 10: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV...
Page 11: ...Operation range Domestic air conditioner 5 Operation range 10...
Page 30: ...Dimensional drawings 8 Dimensional drawings 9 Center of gravity 29 Domestic air conditioner...
Page 38: ...Service diagnosis 37 Domestic air conditioner...
Page 45: ...Service diagnosis 44 Domestic air conditioner...
Page 57: ...57 Do C omestic air ircuit Diagra conditioner ams r...
Page 58: ...58 Do C omestic air ircuit Diagra conditioner ams r 12 2 Module board circuit diagram...