This layout is recommended for heating installations with wide operating water flow variations (radiator thermostatic
valves present in the system). Minimum system volume is guaranteed by a mixing tank (2). Take care when calculating
the volume of water in the installation and only take account of 50% of the mixing tank's volume.
Example: For a useful volume of 70 litres the actual mixing tank volume will be 140 litres.
1
Stop cocks
2
Mixing tank
3
Expansion tank (depending
on
PAC
equipment)
4
Filter or sludge trap
1
4
2
7
1
1
6
1
1
1
1
3
1
5
Recommended hydraulic layout for installing PAC as a stand-alone system on a water network with
a mixing tank.
5
Separator drain-valve
6
Circulation pump
7
Relief valve