background image

LAYOUT –  TR5500

AirTest Technologies Inc

Drawn By

Drawing No.

Rev

6.80

2.85

3.50

5.10

TR-5500 LAYOUT 

dcm

TR5500WLayout.tcw

SCALE 1" = 2"

Circuit Enclosure - Class 1, Division 1, Groups B, C & D

                                

Sensor Enclosure - Class 1, Division 1, Grpups A, B, C &D

                                

GUAC

GUFC

GUAC/GUFC

4

WIRING

AirTest Technologies Inc

Drawn By

Drawing No.

Rev

Signal Return 

Internal Load 

Resistor

with 4-20mA input

Controller

Note - Supply voltage must be 10 volts 

higher than maximum controller voltage.  

On a 0 to 10 volt controller the minimum 

supply voltage required is 20 volts.

For Controller with voltage 

input.    R Value...

5 volt input use 250 ohm

10 volt input use 500 ohm

External Load resistor

TR-5200 WIRING

TR5200WWire.tcw

dcm

B

C

D

+

-

SIG

VR1

SENSOR V

SEN

VR2

VR3

ZERO

SPAN

A

F

E

VR4

CURRENT

+

-

A1

INPUT

B

C

D

+

-

SIG

VR1

SENSOR V

SEN

VR2

VR3

ZERO

SPAN

A

F

E

VR4

CURRENT

+

-

A1

INPUT

+

+

SIG(A)

-

     CT-2100

           &

     CT-1000

CONTROLLERS

12 to 24 VDC

Power Supply

+

-

-

TR-5200/TR5500

TR-5200/TR5500

5

Summary of Contents for TR-5200

Page 1: ...BRATION The sensor transmitter must be connected to the controller Allow the sensor three to five minutes to warm up before calibrating 1 Connect negative lead of voltmeter to test point C YELLOW Connect positive lead of voltmeter to test point D WHITE Apply zero gas to the sensor ambient air may be used if it is certain there are no contaminants in the area Adjust VR2 ZERO to 0 0Volts 0 020V 2 Co...

Page 2: ...o high For the TR 5200 this is 4 25 volts For the TR5500 it is 3 50 volts THE SIX TEST POINTS ON THE LEL BOARD ARE AS FOLLOWS A GROUND BLACK C ZERO TEST POINT YELLOW D SPAN TEST POINT WHITE E 4 20mA TO VOLTS RED B SENSOR VOLTAGE F SYSTEM 10 VDC 0 5V B C D SIG VR1 SENSOR V SEN VR2 VR3 ZERO SPAN A F E VR4 CURRENT A1 INPUT CONTROLLER A1 Fig 1 SENSOR V CONCENTRATION OF CALIBRATION GAS 100 MAXIMUM RANG...

Page 3: ...A input Controller Note Supply voltage must be 10 volts higher than maximum controller voltage On a 0 to 10 volt controller the minimum supply voltage required is 20 volts For Controller with voltage input R Value 5 volt input use 250 ohm 10 volt input use 500 ohm External Load resistor TR 5200 WIRING TR5200WWire tcw dcm B C D SIG VR1 SENSOR V SEN VR2 VR3 ZERO SPAN A F E VR4 CURRENT A1 INPUT B C D...

Page 4: ... company be liable for any consequential or incidental damages however caused No agent dealer or employee of the company has the authority to increase or alter the obligations or limitations of this warranty SPECIFICATIONS Sensing Element Catalytic Bead Standard Range 0 to 100 LEL Combustible gas Gas Sampling Method Diffusion Linearity Linear Operating Temperature 20 C to 50 C 4 F to 122 F Dimensi...