En-10
Function
Function
number
Setting number Default
Details
External
control
46
00
Start/Stop
○
Allow an external controller to start or
stop the system, or to perform an emer-
gency stop.
* If an emergency stop is performed from
an external controller, all refrigerant
systems will be disabled.
* If forced stop is set, indoor unit stops by
the input to the external input terminals,
and Start/Stop by a remote controller is
restricted.
01
Emergency
stop
02 Forced stop
Error
report
target
47
00
All
○
Change the target for reporting errors.
Errors can either be reported in all loca-
tions, or only on the wired remote.
01
Display only
on central
remote
controller
Fan set-
ting when
cooling
thermo-
stat OFF
49
00
Follow the
setting on
the remote
controller
○
When set to 01, the fan stops when the
thermostat is OFF in cooling operation.
Connection of the wired remote control-
ler (2-wire type or 3-wire type) and
switching its thermistor are necessary.
01
Stop
6.4.1. Button name and function
OPERATION indicator lamp (Green)
FILTER indicator lamp (Red)
TIMER indicator lamp (Orange)
6.4.2. Checking the function settings
Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indication pattern
Indoor unit address
Refrigerant address
OPERATION indicator lamp (Green)
ON
Flash (1.0s ON/1.0s OFF)
TIMER indicator lamp (Orange)
Address: tens place (0.5s ON/0.5s OFF)
FILTER indicator lamp (Red)
Address: ones place (0.5s ON/0.5s OFF)
• Indoor unit address example
(Example) ADDRESS : 24
OPERATION indicator
lamp (Green)
TIMER indicator
lamp (Orange)
FILTER indicator
lamp (Red)
10 sec
1 cycle 12 sec
8 sec
ON
OFF
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
0.5s 0.5s 0.5s 0.5s
ON
OFF
ON
OFF
ON
• Refrigerant address example
(Example) ADDRESS : 30
OPERATION
indicator lamp
(Green)
TIMER indicator
lamp (Orange)
FILTER indicator
lamp (Red)
9 sec
1 cycle 12 sec
ON
OFF
1.0s
1.0s
1.0s
1.0s
1.0s
1.0s
1.0s
0.5s 0.5s 0.5s 0.5s 0.5s 0.5s
ON
OFF
ON
OFF
OFF
• Setting
details
Function number
Item
Setting number
01
Indoor unit address
00 to 63
02
Refrigeration address
00 to 99
For use with a remote controller, set all rotary switches to 0, and refer to “6.1. Setting the
address” for details.
All switches are set to 0 at the factory.
(2) Others
Indication pattern
Indicator Name
Indication pattern
OPERATION indicator lamp (Green)
Function number; tens place (0.5s ON/0.5s OFF)
TIMER indicator lamp (Orange)
Function number; ones place
(0.5s ON/0.5s OFF)
FILTER indicator lamp (Red)
Setting number: (0 to 9) (0.5s ON/0.5s OFF)
(Example) Function : 31, Setting number : 2
OPERATION
indicator lamp
(Green)
TIMER indicator
lamp (Orange)
FILTER indicator
lamp (Red)
11 sec
10 sec
9 sec
1 cycle 12 sec
ON
OFF
0.5s 0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s
0.5s 0.5s 0.5s
ON
OFF
ON
OFF
6.5. Connecting the wired remote controller
(If necessary)
In order to connect the wired/simple remote controller to the external switch controller, the
wire assembly (Accessories) which is attached to the indoor unit needs be connected to the
end of remote controller cable.
(1) Use a tool to cut off the terminal on the end of the remote controller cable, and then
remove the insulation from the cut end of the cable.
For 2-wire type
20 mm
For 3-wire type
20 mm
(2) Connect the remote controller cable with connecting cable with solder. IMPORTANT:
Be sure to insulate the connection between the cables.
For 2-wire type
Solder and insulate the connected parts.
Connecting cable
(Accessories)
Cut and insulate
Remote controller
cable (non polar)
Red
White
Black
For 3-wire type
Solder and insulate the connected parts.
Connecting cable
(Accessories)
Remote controller
cable
Red
Red
White
Black
Black
White
For dual control or group control
9377773098-01_IM.indb 10
9377773098-01_IM.indb 10
7/12/2012 3:05:25 PM
7/12/2012 3:05:25 PM
Summary of Contents for ASHE07GACH
Page 17: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 29 PM 7 12 2012 3 05 29 PM...
Page 33: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 36 PM 7 12 2012 3 05 36 PM...
Page 49: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 43 PM 7 12 2012 3 05 43 PM...
Page 65: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 51 PM 7 12 2012 3 05 51 PM...
Page 81: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 05 58 PM 7 12 2012 3 05 58 PM...
Page 97: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 06 PM 7 12 2012 3 06 06 PM...
Page 113: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 14 PM 7 12 2012 3 06 14 PM...
Page 129: ...9377773098 01_IM indb 16 9377773098 01_IM indb 16 7 12 2012 3 06 22 PM 7 12 2012 3 06 22 PM...