AirStage ARXC72GATH Installation Manual Download Page 11

En-10

]1

6.6. External input and external output (Optional 

parts)

Controller PCB

(CNA03)

(CNA01)

Apply voltage terminal

(CNA04)

(CNA02)

Dry contact 
terminal

DIP switch
(SET 2)

OFF ON

SW1

SW2

SW3 SW4

Output terminal
(CNB01)

(1) External input

•  Indoor unit can be Operation/Stop or Emergency stop or Forced stop by using indoor 

unit PCB CNA01 or CNA02.

•  “Start/Stop” mode or “Emergency stop” mode or “Forced stop” mode can be selected 

with function setting of indoor unit.

•  Indoor unit can be Forced thermostat off by using indoor unit PCB CNA03 or CNA04.
•  A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
•  Use an external input and output cable with appropriate external dimension, depending 

on the number of cables to be installed.

•  The wire connection should be separate from the power cable line.

Input select

Use either one of these types of terminal according to the application. (Both types of 
terminals cannot be used simultaneously.)

 Apply voltage terminal ([CNA01], [CNA03])

When a power supply must be provided at the input device you want to connect, use the 
Apply voltage terminal ([CNA01], [CNA03]).

Input

de

vic

e 1

Input

de

vic

e 2

Input

de

vic

e 3

Load 

resistance

Load 

resistance

Load 

resistance

*1

DC power supply
12 to 24V

connected unit

*a

*a

*a

P.C.B

CNA01

CNA03

*b

*1  Make the power supply DC12 to 24V. Select a power supply capacity with an ample 

surplus for the connected load.

Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a  The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
 

Provide a load resistance such that the current becomes DC10mA or less.

 

Select very low current use contacts (usable at DC12V, DC1mA or less).

*b   The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.

When connected to Apply voltage terminals of multiple indoor units with a connected unit, be sure 
to make a branch outside the indoor unit using a pull box, etc. as shown on below example.

DC power supply 
12 to 24V

connected unit

Load 

resistance

P.C.B

P.C.B

CNA01

P.C.B

Input

de

vic

e 1

Input

de

vic

e 2

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Load 

resistance

CNA01

CNA01

 Dry contact terminal ([CNA02], [CNA04])

When a power supply is unnecessary at the input device you want to connect, use the Dry 
contact terminal ([CNA02], [CNA04]).

P.C.B

GND

Ch 1

Ch 3

*c

*c

*c

*d

Ch 2

CNA02

CNA04

connected unit

*c  Select very low current use contacts (usable at DC12V, DC1mA or less).

*d  The wiring is different from Apply voltage terminals. Be suf

fi

 ciently careful when wiring.

When connected to Dry contact terminals of multiple indoor units with a connected unit, 

insulate each indoor unit with relay, etc. as shown on below example.

P

o

w

e

r s

u

p

p

ly

 f

o

r r

e

la

y

Indo

or

 unit

Indo

or

 unit

Indo

or

 unit

Input device 2

Input device 1

K1 - K6: Relay

(Device for DC Current)

P.C.B

K1

P.C.B

P.C.B

CNA02

K2

K3

K4

K5

K6

CNA02

CNA02

NOTE :

When connected to multiple indoor units directly, it will cause breakdown.

Operation behavior

 Input signal type

The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB. 

Pulse

The width of pulse 
must be longer than  
200msec.

Edge

DIP switch [Set 2 SW2]

Input signal type

OFF (Factory setting)

Edge

ON

Pulse

 When function setting is “Operation/Stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

 Operation

ON 

 OFF

Stop

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Operation

Ch2

OFF 

 ON

Stop

*  The last command has priority.
*  The indoor units within the same remote controller group operates in the same mode.

 When function setting is “Emergency stop” mode.

[In the case of “Edge” input]

Connector

Input signal

Command

Ch1 of CNA01 or CNA02

OFF 

 ON

Emergency stop

ON 

 OFF

Normal

[In the case of “Pulse” input]

Connector

Input signal

Command

CNA01 or CNA02

Ch1

OFF 

 ON

Emergency stop

Ch2

OFF 

 ON

Normal

*  All indoor units of same refrigerant system stops when Emergency stop operates. 

9365748145-01_IM.indb   Sec1:10

9365748145-01_IM.indb   Sec1:10

7/12/2012   11:09:14 AM

7/12/2012   11:09:14 AM

Summary of Contents for ARXC72GATH

Page 1: ...TION MANUAL DE INSTALACI N APPAREIL INT RIEUR Type conduit UNIDAD INTERIOR Tipo de ducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIO...

Page 2: ...e parts Always consult authorized service personnel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 1 2 1 Precautions for us...

Page 3: ...not install the indoor unit in the following areas Area with high salt content such as at the seaside It will deteriorate metal parts causing the parts to fail or the unit to leak water Area filled w...

Page 4: ...ong enough the indoor unit may fall and cause injuries 1 CAUTION Confirm the directions of the air intake and outlet before installing the unit The unit takes in air from the evaporator side and expel...

Page 5: ...for R410A clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional R22 flare tools to flare R410A pipes the dimension A should be approxima...

Page 6: ...e refrigerant pipe system such as by degrading the refrigerant oil For brazing material use phosphor copper that does not require flux Width across flats Pipe outside diam eter mm in Width across flat...

Page 7: ...ety drain port of the body Install the hose band from the top of the hose within the graphic display area Secure firmly with the hose band 2 Use vinyl adhesive agent to glue the drain piping PVC pipe...

Page 8: ...PVC cable Polar 3 core Use shielded cable in accordance with local rules for remote controller cable 2 Safety drain There is no need to provide a trap for the safety drain If the safety drain is conne...

Page 9: ...the ring terminal s pressure bonding may malfunction and cause the cables to abnormally heat up B For strand wiring 1 Use ring terminals with insulating sleeves as shown in the figure below to connec...

Page 10: ...AUTION When installing a screw on the terminal board do not cut the cable by overtightening the screw On the other hand an undertightened screw can cause faulty contact which will lead to a communicat...

Page 11: ...the indoor unit using a pull box etc as shown on below example DC power supply 12 to 24V connected unit Load resistance P C B P C B CNA01 P C B Input device 1 Input device 2 Indoor unit Indoor unit In...

Page 12: ...V 2V Lo 0V Permissible current 50mA Output select When indicator etc are connected directly Operation indicator Error indicator Indoor unit Fan status indicator connected unit P C B CNB 01 When connec...

Page 13: ...ther electrical circuitry Use conduit hole when external output cable is used Setting for room temperature correction When a remote sensor is connected set the function setting of indoor unit as indic...

Page 14: ...refrigerant system Set to the same refrigerant circuit address as the outdoor unit If working in an environment where the wireless remote controller can be used the addresses can also be set using th...

Page 15: ...ber Default Details Filter indica tor interval 11 00 Default Adjust the filter cleaning interval notifica tion If the notification is too early change to setting 01 If the notification is too late cha...

Page 16: ...d has the proper operation and handling been explained to the user 10 ERROR CODES 1 If you use a wired type remote controller error codes will appear on the remote controller display If you use a wire...