Setting the
minimum
temperature
that allows to
open the bypass
(0-20°C)
MENU 10 - SUPPLY DUCT LIMITS
10 - Supply Duct Limits
11 - Bypass Temperature
12 - Flow Offset
09 - Temperature sensor
08 - AQS Sensor
Set minimum ca-
nal temperature
Set maximum canal
temperature
Enable or disable the unit's rate
reduction if canal minimum is not
reached (enabled by default)
Due to possible condensation on the surface of the ventilation ductwork, it
is recommended to leave enabled the reduction of flow if canal minimum
is not reached.
MENU 11 - BYPASS TEMPERATURE
MENU 12 - FLOW OFFSET
11 - Bypass Temperature
10 - Supply Duct Limits
09 - Temperature sensor
12 - Flow Offset
13 - Fire Flow
12 - Flow Offset
11 - Bypass Temperature
10 - Supply Duct Limits
13 - Fire Flow
14 - Occupancy
Set positive
or negative
pressure
MENU 13 - FIREFLOW
13 - Fire Flow
14 - Occupancy
15 - Boost
11 - Bypass Temperature
12 - Flow Offset
Setting the unit's
rate when the
FIRE contact
opens (input
terminals 15/16)
The FIRE FLOW and OCCUPANCY
modes can not be used simultaneously
One of the modes must be chosen in the
HW setting menu
Selecting the sensor in the supply ductwork
disables the maximum temperature setting
in the ductwork
The FIRE input has the highest priority (it
disables all the other modes, including anti-
freeze protection)