Mechanical Installation

 

Page 5 of 8

 

Page 6 of 8

 

Module adjustment

 

Front Cover Removal

 

Page 7 of 8

 

Module 

locating block

 

3

-

way supply 

connector

 

Two module 

connector pins

 

Module 

locating slot

 

Cable entry

 

PIR lens 

location

 

To remove front cover assembly, first  make sure 

the  fan  is 

off, isolated from the power supply 

and the 

iris shutter is 

fully closed

 

1.

 

Undo  the  locking  screw  at  the  bottom  edge  of  the  cover 

using a screwdriver. 

 

2.

 

Rotate the cover a few degrees anticlockwise until it clicks 

out from the fittings. 

 

3.

 

Remove the cover by pulling it out. 

 

 

 

 

 

 

 

 

 

 

 

To  refit  the  cover,  reverse  the  above  procedure.  The  iris 

shutter  should  be  in  closed  position  after  refit.  If  not,  wait 

approximately 1 min after fan switch off allowing the actuator 

to retract back in the closed position and then refit the cover 

again. 

 

3

 

1

 

2

 

iCON module

 

Module cable 

clamp

 

Terminal block 

fitting (pillars)

 

iCON module overview.

 

A module with Timer and/or Humidistat is supplied pre

-

set, 

but may be adjusted by the installer. All adjustments must be 

done using the supplied Adjustment Tool. 

 

Humidity settings

 

The humidistat is factory pre

-

set at approx. 70% RH (relative 

humidity). Adjusting the 

“%

 

RH

” 

towards 40% will result in fan 

activation at lower humidity (more sensitive). Adjusting the 

“%

 

RH

” 

towards 

“90%” 

will result in fan activation at higher 

humidity (less sensitive). 

 

Time settings

 

The Run on Timer is factory pre

-

set at approx. 15 min. Ad-

justing the 

Timer

” 

towards 

MIN

” 

will result in a timer overrun 

decrease towards 1 or 2 minutes (depends on module). 

Adjusting the 

Timer

” 

towards 

MAX

” 

will result in a timer 

overrun increase towards 30 or 45 minutes (depends on 

module). 

 

 

Warranty

 

Applicable to units installed and used in the United Kingdom. 

 

Airflow Developments Ltd guarantees the iCON range for 

3 years (incl. modules) from date of purchase against 

faulty material or workmanship.

 You can register your 

warranty on

-

line (for more information check at 

www.airflow.com). Warranty only covers the product, not a 

reinstallation if required. 

 

For detailed standard warranty terms and conditions see 

our website or contact Customer Service.

 

Adjustment 

tool

 

Timer control

 

Humidistat 

control

 

Humidistat

 

MIN = 40% RH

 

MAX = 90% RH

 

Timer

 

MIN = 1 or 2 min

 

MAX = 30 or 45 min

 

Module clip

 

© Airflow Developments Ltd.

 

 

Airflow Developments Limited reserve the right, in the interests of continuous develop-

ment, to alter specifications without prior notice. All orders are accepted subject to our 

conditions of sale which are available on request. 

 

 

www.airflow.com

 

UK Head

-

Office

 

AIRFLOW DEVELOPMENTS Ltd

 

Aidelle House, Lancaster Road

 

Cressex Business Park

 

High Wycombe

 

Buckinghamshire 

 

HP12 3QP

 

United Kingdom

 

 

Tel:        +44 (0) 1494 525252

 

Email:    [email protected]

 

Web:      www.airflow.com

 

Czech Republic

 

AIRFLOW LUFTTECHNIK GmbH

 

o.s. Praha

 

Hostýnská 520

 

108 00 Praha 10

 

Malešice

 

Czech Republic

 

 

 

Tel:        +42 (0) 2 7477 2230

 

Email:    [email protected]

 

Web:      www.airflow.cz

 

Germany

 

AIRFLOW LUFTTECHNIK GmbH

 

Wolbersacker 16

 

53359 Rheinbach

 

Germany

 

 

 

 

 

Tel:         +49 (0) 222 69205 0

 

Email:     [email protected]

 

Web:       www.airflow.de

 

80000440 Issue 3 08/21

 

Reviews: