21
Results for SAP calculations (at minimum flow rate condition)
This product has only been tested with rigid ductwork and the data are not applicable for SAP
calculations if installed with flexible ductwork.
Table Q2 – Systems with rigid ductwork only
Exhaust terminal
configuration
Fan speed
setting
Specific
fan
power
(W/l/s)
Heat
exchange
efficiency
(%)
Energy Saving
Trust Best Practice
Performance
Compliant
K
1 additional wet
room
100%
Variable
0.73
91
Yes
K
2 additional wet
rooms
100%
Variable
0.72
90
Yes
K
3 additional wet
rooms
100%
Variable
0.79
89
Yes
K
4 additional wet
rooms
100%
Variable
0.93
88
Yes
K
5 additional wet
rooms
100%
Variable
1.06
87
No
These figures are entered into either:
(a) In the case of SAP software amended to SAP 2005 version 9.81 allowing direct entry of MVHR data,
the SAP software, or
(b) In the case of SAP software amended to SAP 2005 version 9.81 not allowing direct entry of MVHR
data, the SAP Q MVHR Calculation Spreadsheet v9.81 and the results from the spreadsheet into the
Special Features part of the SAP 9.81 software, or
(c) In the case of SAP software to SAP 2005 version 9.80, the SAP Q MVHR Calculation Spreadsheet
v9.80 and the results from the spreadsheet into the Special Features part of the SAP 9.80 software.
They must NOT be entered directly into SAP 2005 version 9.80 software