OPERATING INSTRUCTIONS

Adjustment of supply air temperature 

and summer/winter function

The  temperature  of  air  coming  to  the  dwelling  can  be  adjusted 

between circa +10 °C and +30 °C. When there is a light on the 

post-heating indicator, post-heating is activated and the unit heats air 

as needed. The need for heating depends on the setpoint of supply 

air temperature. 
When there is no light on the post-heating indicator, post-heating is 

off. This means that the summer function is activated for the ventilation 

unit.  The  unit  has  a  motorised  summer/winter  function.  When  the 

summer function is on, the heat recovery cell is bypassed as soon 

as  outdoor  air  temperature  has  risen  above  the  setpoint.  See  the 

setpoint for cell bypass, factory s12 ºC. When outdoor air 

temperature goes below the setpoint (factory s12 °C), the 

unit starts to recover heat.
Two  different  kinds  of  supply  air  temperature  adjustment  can  be 

chosen at the unit: constant temperature control or cascade control. 

In constant temperature control, the unit controls the temperature of 

supply air directly in accordance with the measurement information 

on  the  temperature  of  supply  air  blown  to  the  ventilation  area.  In 

cascade control, the unit controls supply air temperature according 

to the temperature of air extracted from the ventilation area. The unit 

calculates the difference between the air extracted and the setpoint 

for supply air and uses this difference to control the need for post-

heating.

Winter function of ventilation unit

A set of parameters has been set at the factory for the freezing of 

the heat recovery cell (3.21 and 3.22).When these parameters are 

undercut, the ventilation unit melts the heat recovery cell utilising the 

heat of extract air. 
Melting  is  done  by  stopping  the  supply  air  fan  (3.20.  Choosing 

melting mode) or by bypassing the heat recovery cell on the supply 

air side (factory setting).
If  the  bypassing  the  heat  recovery  cell  is  chosen  as  the  melting 

mode,  the  relationship  between  the  supply  and  extract  air  fl ows 

does not change. This prevents the formation of a vacuum inside, 

which may be harmful in some cases. In this case the electric resistor 

heats the cold air coming from outside during the melting period to 

Remember!

Switch post-heating off when it starts to get too warm in the 

dwelling because of warm weathers.

Switch post-heating on again when it gets cooler in autumn.

Post-heating indicator light

Maintenance reminder 

symbol

Maintenance reminder

•   The maintenance reminder switches on the maintenance 

reminder symbol( ) on the main display of the control panel 

at defi ned intervals, the factory setting being 4 months.

•   The maintenance reminder symbol is acknowledged at 

the main display of the control panel. (See the operating 

instructions for control panel, Section 3.1.)

•   The interval can be set between 1 and 15 months at the 

control panel.

Fireplace switch function/booster

Fireplace switch function

(See the operating instructions for control panel, Section 3.12.)
•   The fi replace switch stops the extract air fan for 15 minutes and 

produces overpressure in the ventilation zone. This makes it 

easier to light a fi replace.

 

The function is started on the main display of the control panel 

by simultaneously pressing and holding down the + and – 

buttons for 2 seconds.

•   The function can also be started at a separate auto-reset push-

button switch, wired from the connection box of the unit for 

example to a wall in the fi replace room. Upon each pressing, 

the stopping function continues for 15 minutes (the switch is not 

included in the delivery).

•   During the function, the fi replace/booster switch symbol ( ) is 

visible on the main display of the control panel.

NOTE! The starting of the extract air fan may weaken draught in the 

fi replace! In winter, this situation may disturb the winter function of the 

unit. The situation will normalise in a while, after the fi replace function 

stops.

Booster switch function

(See the operating instructions for control panel, Section 3.12.)
•   The booster switch function raises fan speed to the set maximum 

fan speed for 45 minutes.

 

The function is started on the main display of the control panel 

by simultaneously pressing and holding down the + and – 

buttons for 2 seconds.

•   The function can also be started at a separate auto-reset 

push-button switch, wired from the connection box of the unit 

to for instance a wall in a classroom. Upon each pressing, the 

boosting function continues for 45 minutes.

•   During the function, the fi replace/booster switch symbol ( ) is 

visible in the main display of the control panel.

•   The function is chosen at the control panel.

Fireplace/booster switch symbol

Fault signal relay (remote monitoring)

•   The fault signal relay has potential-free contacts 

(24 VDC, 1 A).

•   The contacts provide information on various failure modes 

of the unit.

•   Alarm of high carbon dioxide content switches the relay at 

1-second intervals.

•   In other fault situations, the contacts are closed.

the temperature desired (2.6. Setting supply air temperature). If the 

temperature desired is high compared to outdoor air temperature, 

the unit decreases the supply and extract air fl ows in order to attain 

the desired supply air temperature.
A normal melting period varies from 15 to 45 minutes depending on 

the amount of ice and the volume of the extract air fl ow.
The unit operates optimally on the factory settings in normal operation 

in dwellings and detached houses. The parameters only need to be 

touched in extreme problem situations. Examples of such situations 

are high humidity loads such as a swimming pool or if there is a 

detrimental amount of ice in the exhaust air duct.

DV145SE

Summary of Contents for DUPLEXVENT DV145SE

Page 1: ...g maintenance and technical instructions Electrical connection 230 V 50 Hz 11 9 A plug Degree of protection provided by enclosures IP34 Fans Extract air 150 dm3 s 100 Pa direct current DC Supply air 140 dm3 s 100 Pa Heat recovery Cross counter flow heat recovery cell 80 Heat recovery bypass Automatic Electric post heating unit standard 900 W 3 9 A Additional heater 1500 W 6 5 A Fans Supply air G4 a...

Page 2: ...ighest measuring result 1 to 2 carbon dioxide sensors can be connected as options to the DUPLEXVENT DV145SE unit The adjustment is switched on off and if needed the setpoint 500 2000 ppm is set at the control panel The factory setting is 900 ppm The recommended maximum carbon dioxide content in good indoor air is circa 1 000 ppm During control the control panel can be used to raise fan speed to th...

Page 3: ...months The maintenance reminder symbol is acknowledged at the main display of the control panel See the operating instructions for control panel Section 3 1 The interval can be set between 1 and 15 months at the control panel Fireplace switch function booster Fireplace switch function See the operating instructions for control panel Section 3 12 The fireplace switch stops the extract air fan for 1...

Page 4: ... can chan ge setpoints for the ventilation unit 2 3 Week clock control Week program on Week clock control can be switched on with the button and off with the button Week clock control is on when the week clock control symbol is in the main display In week clock control the base fan speed and supply air temperature of the unit are adjusted in accordance with the programme as described in Section 4 ...

Page 5: ...electric radiator is selected with the and buttons depending on the type of post heating radiator the unit is equipped with Note Choosing the wrong type of post heating may cause a faulty post heating function 3 18 Choosing additional heater for unit Extraheater type Electric rad An electric or MLV radiator is chosen according to ventilation unit type with the and buttons This unit can be used onl...

Page 6: ...ir fan can be decreased by decreasing the percentage Move the cursor with the arrow keys and change values with the and buttons Note that to exit and save when the programming is finished move the cursor below the word Exit and press or Changes in fan speed Sp and supply air temperature Temp are only made for the hours desired in other cases use N no change to previous Monday d 1 07 00 h 7 fan spe...

Page 7: ...od operation of the ventilation unit and the best filtering result The replacement interval of filters depends on dust content in ambient air It is recommended to replace fans in spring and autumn but at least once a year MAINTENANCE INSTRUCTIONS Filters Heat recovery cell Heat recovery cell When you replace the filters you are also advised to check the cleanliness of the heat recovery HR cell D a...

Page 8: ... and crank the plastic lock to the right using for instance a chisel figure 6 The fan then falls down and can be pulled out of the unit Disconnect the quick coupling of the fan conductors When needed detach the intermediate shaft of the bypass damper from the end of the partition wall figure 7 Condensing water During the heating season humidity of extract air condenses into condensing water Water ...

Page 9: ...is displayed and the unit operates at speed 1 check the fan speed Wiring fault in the carbon dioxide sensor in the control panel or in the humidity sensor or the cable is of the wrong type Contact a maintenance company The connections have to be checked and corrected if necessary 9 Freezing alert message is displayed and the unit is stopped Antifreeze of the water circulating radiator is active NO...

Page 10: ...ncy of the octave band Hz 63 41 50 56 58 59 64 67 69 35 45 49 51 51 56 58 58 125 45 53 56 59 62 65 68 71 33 43 46 49 49 54 56 59 250 50 54 57 61 63 66 68 70 24 32 37 40 40 45 47 49 500 48 53 56 59 60 63 65 68 37 43 46 48 48 52 54 56 1000 45 54 57 60 62 64 66 67 30 36 39 42 42 46 48 50 2000 35 46 50 55 58 61 64 66 22 32 34 38 38 43 45 48 4000 26 41 46 51 54 58 60 63 16 20 22 25 25 31 33 36 8000 21 ...

Page 11: ... it must be replaced by the manufacturer authorised maintenance company or other qualified person in order to avoid danger T Supply air fan P Extract air fan M1 Protective voltage transformer 230 VAC 16 VAC L Earthed cord TK Safety switch R1 Additional heating radiator 90 C and 130 C with overheat protection R2 Post heating radiator 90 C and 130 C with overheat protection M Damper motor 24 V DC Wi...

Page 12: ...e In this case remove one of the control panels and change the address of the other panel The above mentioned situation can arise in connection with the later installation of an additional control panel External electrical connection DUPLEXVENT DV145SE METAL M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 2 TWISTED PAIR 1 TWISTED PAIR NOTE Faulty connection of the wire DESTROYS CONTROL PANEL NOTE Faulty c...

Page 13: ... Condensing water connections The delivery includes a water seal By connecting a pipe to the water seal the water condensing from extract air can be led to a floor drain not directly to the drain The pipe must not rise after the water seal The unit has to be mounted horizontally level so that condens ing water can get freely out of the unit The minimum distance between the top of the unit and the ...

Page 14: ...What the units include can vary depending on the sales area MOUNTING Attic floor penetration plate option When an attic floor penetration plate is used the tightness of the vapour barrier has to be ensured Minimum distance to side walls is 15 mm 547 8 747 15 15 0 DV145SE ...

Page 15: ...art Code 12 G4 coarse filter 978047 13 Bypass assembly indicate if 3475900 Right or left handed 14 Damper motor 930613 15 Extract air outlet 985035 16 Protective voltage transformer 940150 17 Motherboard 949045 18 Safety switch 948370 19 Additional heater 1500 W 942220 20 Post heater 900 W R 942211 Post heater 900 W L 942210 No Part Code 21 Door assembly 3476000 22 Door latch assembly 3355900 23 N...

Page 16: ...mpliance with this requirement by an assessed and registered Competent Person should follow a Best Practice process and adopt air flow measurement Method A The Unconditional Method using a suitable UKAS certified measuring instrument Generically referred to as a Zero Pressure Air Flow Meter or Powered Flow Meter Further information on this method is detailed in NHBC Building Regulations Guidance N...

Reviews: