Airflow Instruments AV 30 Operating Instructions Manual Download Page 5

 

The instrument will function satisfactorily in an angular position but 
should not be used in airstreams which are smaller than the entire face 
area of the measuring head (113mm diameter).  The AV30 is calibrated 
for use in free air conditions.  For smaller airstreams TSI

 

Instruments 

Ltd. thermal type anemometers are recommended. 
 
 

4.2

 

Checking air velocity or volume flow rate over larger areas. 
When checking air velocity or volume flow rate over larger areas, a 
number of ‘spot’ readings should be taken and recorded to give 
coverage over the whole area. 
 
When taking ‘spot’ readings, it should be noted that quite large 
variations might be observed between individual readings.  In general, 
the more readings taken, the more accurate the result will be.  It does 
not matter if the positions of the readings overlap somewhat, so long as 
they are equally spread to cover the entire area. 

 
 

5.

 

Use on Grilles 
Note:

 See Comments under section 7 ‘Possible sources of error’.  Avoid 

intrusion of the hand, arm or handle of the instrument into the face area of 
the grille.  The blockage effect created by this would cause artificially high 
velocity over the remainder of the grille, leading to additional errors. 
Better measuring conditions can be obtained on grilles with adjustable 
direction vanes if the vanes on the grilles are temporarily straightened 
before making measurements.  This should not significantly affect the flow 
rate so long as any built in dampers are not accidentally disturbed.  It is 
advisable to use the aperture, not the surface area of the grille in any flow 
calculations. 
 
The instrument is suitable for both supply and extract grilles, and the 
procedure for both is the same except that the measuring head must be 
rotated through 180

o

 to align the direction arrow correctly. 

Whilst it is acceptable to hold the anemometer head against the grille in 
extract it is usually recommended to hold it slightly away from the grille 
face on supply to avoid excessive turbulence and any vena-contracta 
effects. 

 
 
 

Summary of Contents for AV 30

Page 1: ...1 AV30 OPERATING INSTRUCTIONS Please read these instructions carefully before using the instrument Shortform instructions appear on the back of the instrument 9021435 A 0805...

Page 2: ...DC offset which should be taken into account when taking readings The cable connected to the 0 1 volt output should not be more than 3 metres long 2 BATTERY INFORMATION 2 1 The AV30 is supplied with...

Page 3: ...battery symbols at both ends of the top line of the display The instrument will still operate correctly but only for a limited time so the batteries should be replaced as soon as possible Also use of...

Page 4: ...to 100 in steps of ten Use the and keys to select the level of averaging desired then press the key to confirm selection 3 1 5 Backlight Turns on and off the screen backlight press the key to toggle...

Page 5: ...e Comments under section 7 Possible sources of error Avoid intrusion of the hand arm or handle of the instrument into the face area of the grille The blockage effect created by this would cause artifi...

Page 6: ...lle particularly if this is of the type having adjustable direction vanes and or dampers The airstream issuing from such a grille is invariably very disturbed consisting of many small areas of high ve...

Page 7: ...G ALTERING THE CALIBRATION WILL INVALIDATE TSI INSTRUMENTS LTD RESPONSIBILITY FOR CALIBRATION UNDER WARRANTY The unit will monitor each time the calibration is effected If the calibration routine is i...

Page 8: ...ephone 001 651 490 2811 Fax 001 651 490 3824 WWW http www tsi com The statements and opinions contained in this document are made in good faith Whilst every effort has been made to provide reliable in...

Page 9: ...ding 1 digit Volume Flow Ranges Accuracy 35mm Head 0 02 1800 m sec 2 1 800 000 l sec 2 6 480 000 m3 hr Calibrated to better than 2 of reading 1 digit 2 3 700 000 ft3 min Calibrated to better than 2 of...

Page 10: ...tandards EN50081 1 Radiated Emissions and EN50082 1 Radiated and ESD Immunities QUALITY ASSURED TO ISO 9001 TSI Instruments Ltd August 2005 Lancaster Road Part No 9021435 Rev A Cressex Business Park H...

Reviews: