ULTIMA
™ REMOTE AIR COOLED
Chillers
44
Chillers
Technical Manual : Part No 6259485 V1.15.0_08_2018
Technical Data - Ecodesign
URAC200DQ, URAC225DQ, URAC240DQ, URAC250DQ, URAC270DQ
Notes:
URAC200DQ
URAC225DQ
URAC240DQ
URAC250DQ
URAC270DQ
SEPR
1,3,5
4.79
5.03
4.64
5.18
4.91
SEPR Tier
Tier 1 (2018)
Tier 2 (2021)
Tier 1 (2018)
Tier 2 (2021)
Tier 1 (2018)
Annual Electricity
Consumption
kWh/a
352849
373658
411281
404439
442844
Rated Refrigerant
Capacity P
A
1,3,5
kW
227.2
252.6
256.5
281.5
292.2
Rated Power Input D
A
kW
73.1
77.8
86.3
84.8
97.6
Rated EER
DC,A
3.11
3.25
2.97
3.32
3.00
Declared Refrigerant
Capacity P
B
1,3,5
kW
245.3/199.7
272/211.6
277.8/232.4
302.3/228
318.4/272.4
Declared Power Input
D
B
kW
60.0/49
64.1/49.2
72.1/60.5
69.3/51.7
80.3/68.6
Declared EER
DC,B
4.09/4.08
4.24/4.30
3.86/3.84
4.36/4.41
3.97/3.97
Declared Refrigerant
Capacity P
C
1,3,5
kW
207.7/159.6
220.1/156.5
246.3/197.7
314.6/236.6
291.1/227.9
Declared Power Input
D
C
kW
42.1/34.2
42.7/31.8
51.9/43.7
59.3/44.5
57.4/47.3
Declared EER
DC,C
4.94/4.66
5.16/4.92
4.74/4.52
5.31/5.31
5.07/4.81
Declared Refrigerant
Capacity P
D
1,3,5
kW
207.7/159.6
220.1/156.5
249.9/200.7
236.6/159.4
295.7/231.8
Declared Power Input
D
D
kW
40.1/32.3
41.3/30.4
48.1/40.1
43.2/30.7
53.0/43.3
Declared EER
DC,D
5.18/4.95
5.33/5.14
5.20/5.01
5.48/5.20
5.58/5.36
SSCEE
2,3,5
%
147.0
162.4
134.2
166.2
143.2
SSCEE Tier
Not
Compliant
Tier 2 (2021)
Not
Compliant
Tier 2 (2021)
Not
Compliant
Rated Cooling
Capacity P
rated,c
2,4,5
n/a
253.5
n/a
282.6
n/a
Declared Cooling
Capacity 35°C Pdc
2,3,5
kW
n/a
252.6
n/a
281.5
n/a
Declared EER
d
35°C
n/a
3.25
n/a
3.32
n/a
Declared Cooling
Capacity 30°C Pdc
2,3,5
kW
n/a
218.1/157.2
n/a
233.3/158.9
n/a
Declared EER
d
30°C
n/a
4.07/3.99
n/a
4.13/4.03
n/a
Declared Cooling
Capacity 25°C Pdc
2,3,5
kW
n/a
170.2/87.0
n/a
171.4/87.6
n/a
Declared EER
d
25°C
n/a
4.80/4.14
n/a
4.82/4.16
n/a
Declared Cooling
Capacity 20°C Pdc
2,3,5
kW
n/a
93.4/0
n/a
94.3/0
n/a
Declared EER
d
20°C
n/a
5.06/0
n/a
5.08/0
n/a
Sound Power Level
L
WA
dB(A)
n/a
88.0
n/a
90.0
n/a
Off mode P
OFF
kW
n/a
0.237
n/a
0.237
n/a
Thermostat-off mode
P
TO
kW
n/a
0.959
n/a
1.104
n/a
Standby Mode P
SB
kW
n/a
0.245
n/a
0.245
n/a
Crankcase heater
mode P
CK
kW
n/a
0.208
n/a
0.208
n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections
.