Condensing Units
ULTIMA COMPACT
Condensers & Condensing Units
15
Installation & Maintenance : 6259675 IM V1.9.0 04/2016
Chill
ers
ULT
IM
A CO
M
PACT
Installation Data
ANTI VIBRATION MOUNTING
– OPTIONAL
COMPONENTS:
1
Locating Screw
2
Retaining Nut & Washer
3
Levelling Screw
4
Levelling Lock Nut
5
Retaining Studs
6a
Upper Retaining Nuts
6b
Lower Retaining Nuts
7
Spring assembly
8
Pressure Plate
9
Top Plate
10
Bolting-down holes
2
1
6a
5
6b
10
9
8
7
3
4
DIMENSIONS:
B
A
C
D
E
F
E
A
(1)
B
C
D
E
FØ
UCC30-70
2
S
P
R
IN
G
162
110
180
148
16
11
UCC75, 80, 100, 125 & 150
UCCU30-70
UCCU75, 80, 100, 125 & 150
UCFC75-150
UCC110, 130, 160-450
4
S
P
R
IN
G
162
130
225
186
20
16
UCCU110, 130, 160-450
UCFC160-450
UFC200-750
URAC75-450
USC200-750
UWC75-450
(1)
Unloaded dimension
(2)
Refer to relevant
Loose Parts Instructions
sheet for positioning of each mount.
INSTALLATION
1
Locate and secure mount using bolting down holes (10) in base plate.
2
Ensure mounts are located in line with the unit base.
3
If applicable, remove compressor enclosure covers to allow access to mount fixing holes in
the unit base.
4
Lock the upper retaining nuts (6a) to the underside of the top plate (9) before a load is
applied.
5
Remove retaining nut and washer (2), lower the unit onto the mounts and replace retaining
nut and washer.
6
Beginning with the mount with the largest deflection, adjust the height of each mount using
the levelling screw (3).
CAUTION
Mountings must be adjusted incrementally in turn. Do not fully adjust 1 mount at a time as
this may overload and damage springs.
7
When all mounts are level, lock each into place using the levelling lock nut (4).
8
Lock all retaining nuts (6a and 6b) to the extreme ends of the retaining studs (5).
CAUTION
Do not connect any services until all anti vibration mounts have been fully adjusted.