TURBOCHILL Chillers
Chillers
14
Installation Manual : 6703052 05/2008
Installation Data
•
Employ lifting specialists
•
Local codes and regulations relating to the lifting of this type of equipment should
be observed
•
Use the appropriate spreader bars/lifting slings (provided by others) with the eye
bolts/lugs provided
•
Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided;
each individual chain must be capable of lifting the whole unit
UNIT LIFTING
•
Lifting eye bolt/lug dimension: 40mm
Do not use 1 chain between 2 lifting points to avoid load shift.
IMPORTANT
Only use lifting points provided.
Chains/slings MUST NOT interfere with the casing or fan assembly to
avoid damage.
Lift the unit slowly and evenly.
If the unit is dropped, it should immediately be checked for damage and reported
to Airedale.
LIFTING DIMENSIONS
8 - 10 Fan
A1
C
B
2300
12 - 20 Fan
A1
C
B
C
A2
2300
A1 (Min)
A2 (Min)
B
C
TCC1xxx08Xxx
mm 4000
N/A
520
3200
TCC1xxx10Xxx
mm
4000
N/A
846
3500
TCC1xxx12Xxx
mm 4000
5000
520
4000
TCC1xxx14Xxx
mm
5000
5000
520
4650
TCC1xxx16Xxx
mm 5000
5000
520
5000
TCC1xxx18Xxx
mm
6000
5000
520
5650
TCC1xxx20Xxx
mm 7000
5000
520
6650