![AIREDALE DR Series Technical Manual Download Page 24](http://html.mh-extra.com/html/airedale/dr-series/dr-series_technical-manual_2876532024.webp)
Dry Cooler
Condensers
24
Dry Coolers Technical Manual 9308503 V2_06_2020
Te
ch
ni
ca
l
Mechanical Data
(1)Nominal data based on 35°C ambient and 45/40°C Water entering / leaving. All performance data is supplied in accordance with BS EN 14511-1:2013
(2) Overall dimensions for clearance
DR10
DR12
DR15
Total Heat of Rejection DR
(1) kW
11.1
13.7
15.3
Dimensions - Horizontal
(2)
H x W x L
mm
1167 x 1000 x 1095 1167 x 1000 x 1095
1167 x 1000 x 1095
Dimensions – Vertical
(2)
H x W x L
mm
1126 x 1167 x 1100 1205 x 1167 x 1100
1126 x 1167 x 1100
Weight
Machine
kg
96
106
110
Construction
Material/Colour
Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL
7035)
Dry Cooler
Air Cooled - Copper Tube/Turbulated Aluminium Fins
Total Face Area
m²
0.91
0.91
0.91
Nominal Airflow
m³/s
2.3
3.3
1.9
Discharge
H Horizontal or -V Vertical (Please Specify at Order)
Std Fan & Motor
AC
EC
AC
Quantity
1
1
1
Diameter
mm
630
710
630
Maximum Speed
rpm
895
930
895
Dry Cooler
Internal Water Volume
L
6.6
6.6
11.9
Nominal Flowrate
l/s
0.53
0.65
0.7
Pressure Drop
kPa
11.9
17.8
20.7
OPTIONAL EXTRAS
EC Fan
Dimensions - Horizontal
H x W x L
mm
1167 x 1000 x 1095
-
1167 x 1000 x 1095
Dimensions - Vertical
H x W x L
mm
1205 x 1167 x 1100
-
1205 x 1167 x 1100
Weight
Machine
kg
88
-
101