Recommended Pipework (External to Unit)
This diagram shows the valid install for a 2 pipe Artus unit; another manifold set would be required for a 4 pipe Artus unit.
Please contact Airedale for more information.
DOC
DOC
Strainer
Pump
Automatic air vent
Pressure test point
Key
Isolating valve
Fixed orifice flow measurement device
(orifice plate)
Drain off cock
Do not use a differential pressure control valve and a PICV in the same system. These two
components will work against each other and will affect performance.
CAUTION
Recommended Pipework Installation - 2 Pipe Cooling Only
2 pipe cooling
only
2 pipe cooling
only
2 pipe cooling
only
2 pipe cooling
only
Airedale (or third party) air-cooled chiller
This is a simplified diagram. All the components highlighted in the Recommended Pipework
(External to Unit) section to be included on all circuits.
IMPORTANT