background image

10 

Commissioning of the Unit

1.   Turn the power on at the circuit breaker.

2.  Press the ON/OFF button and press the MODE button to 

select FAN.

3.  Cycle through the LOW, MED and HIGH fan speeds checking 

that all speeds run.

4.  Set mode to COOL, adjust temperature via up/down 

buttons to 4˚C below the display temp (ie room temp) 
compressor will start within three minutes.

5.  Set mode to HEAT, similarly set temperature to 4˚C above 

the display temperature. Compressor will start within three 
minutes. After a few minutes the fan will start and warm 
air will be apparent. 

NOTE: Regardless of the mode selected there will always be at 
least a 3 minute delay before the compressor starts. If the unit 
is turned off it is important that the compressor be given at 
least 3 minutes before being re-activated

Maintenance

I.  PLENUM FILTERS

The plenum fi lters are the only parts that require routine 
maintenance. They must be cleaned periodically to ensure that 
they do not become clogged with dust and other particles.

Blocked fi lters must be cleaned frequently to maintain cooling 
& heating performance

To clean the two plenum fi lters, fi rst remove them both from 
the plenum by pulling them out of the assembly.

Fig 17: Plenum fi lter when removed.

The state of the fi lters can be ascertained from its appearance, 
if they appear clogged then they should be cleaned. Generally 
the fi lters can be cleaned suffi ciently by tapping them 
together to shake loose the dust and particles trapped inside.
 

       WARNING

Airborne particles can pose a health risk, particulalry to young 
children and the elderly. Ensure that fi lters are cleaned in a 
safe and well ventilated area.

If a more thorough clean is required then the fi lters can be 
washed out using warm soapy water. Care must be taken to 
avoid ripping the fabric.

The fi lters should be cleaned every two weeks or more when in 
use. Prolonged use, higher concentrations of airborne particles 
and various other factors may result in the fi lters needing to 
be cleaned more often.

Replacement fi lters can be ordered directly from Aircommand. 

II.  MOUNTING BOLTS

Aircommand suggests that the hold down bolts are initially 
checked for tightness within the fi rst 3 months of installation, 
and thereafter every 12 months if the van is in constant use.

III.  STORAGE 

The air conditioner should be run on a routine basis to ensure 
the components remain in working order. 

If the van is in storage or is to remain unoccupied for an 
extended length of time it is recommended that the air 
conditioner is allowed to run uninterrupted for 20-30 minutes 
once every six months.

For long term storage outdoors, or to protect your Sparrow 
from winter storms and weathering when not in use, a 
protective cover can be purchased from Aircommand, please 
call for details.

IV.  WARRANTY CLAIMS

The unit comes with a one year manufacturer’s warranty from 
date of purchase. It is IMPORTANT that you read and 
understand the conditions of the warranty agreement which 
are included with the unit. 

If you have a claim please contact Aircommand directly on      
(+61) 8 8345 8444, alternatively you can fax (+61) 8243 0628 or 
email [email protected]

Please have your unit serial number ready.

Summary of Contents for 5860001

Page 1: ...hnician Failure to properly install the unit or attempting to modify it in any way can be extremely hazardous and may result in property damage and personal injury Aircommand will not be held responsible for problems relating to incorrect or improper installation methods INFORMATION INSTALLATION COMMISSIONING MAINTENANCE SPECIFICATIONS SPARE PARTS WIRING DIAGRAM TROUBLE SHOOTING OPERATING INSTRUCT...

Page 2: ...Position the vehicle so that the annex will face north and protect the windows from direct radiation Turning off unneeded appliances that might increase the heat load inside the van Cook outside if possible Park the caravan RV in a shaded position if possible In periods of extreme high temperature it is recommended to start the air conditioner earlier in the morning to greatly improve its ability ...

Page 3: ...o nation wiring regulations and in particular AS3001 2008 DO NOT attempt to modify or add components to the installation procedure This equipment must only be serviced by a licensed refrigeration mechanic If your installation varies from the method outlined please contact Aircommand for specialty advice WARNING Failure to properly install the unit or attempting to modify it in any way can be extre...

Page 4: ...5 from the horizontal and the rear of the unit should never be higher than the front when in use Contact Aircommand if your installation differs significantly The above outline on the left shows the minimum clearance required around the Sparrow Mk4 unit on the roof of the vehicle distances shown are calculated from a 14 square hole 356 x 356mm The above outline on the right shows the minimum clear...

Page 5: ...battery Failure to do so may result in personal injury or death TIP Always use crawl boards across the roof to avoid damage Be sure to allow space for power cable The roof cavity must be framed to support the units weight 20mm min Longitudinals must be fixed securely to transverse roof members Fig 3 Shows an ideal roof structure with strong longitudinals and a 14 hole boxed Fig 5 Left hand picture...

Page 6: ...h the corresponding holes on the weather collar Fig 6 Apply sealant around bolt holes and then position unit over the weather collar and set down gently 5 Connect Electrical Supply This unit MUST be installed in accordance with SAA Wiring regulations and in particular AS3001 2008 Refer Fig 7 for position of terminal block Connect electrical supply to terminal strip Note position of active neutral ...

Page 7: ...7 Assemble Duct Thread a hold down bar onto the M8 bolt and push the bolt almost all the way into the hole in each corner of the brace Fig 9 Leave a 10mm gap between the hold down bar and the recess in the plastic brace This will allow for easier engagement with the four corresponding threaded holes in the unit Turn the assembly over and add the black plastic duct work to the top of the assembly w...

Page 8: ...hten the four M8 bolts with the threaded inserts in the rooftop unit Recommended tightening torque of the bolts is 7 N m 5 2 lbf ft As the bolts are tightened ensure that the hold down bars slot into their recesses in the brace Fig 11 Fig 11 Raise the duct assembly up to the roof hole ensuring the black plastic duct work forms a tight fit around the evaporator fan underneath the unit Then engage t...

Page 9: ...ements by pulling them out of the plenum and use the six self tapping counter sunk screws to secure the cover s edges to the caravan ceiling Fig 16 In some instances a very small pilot hole may need to be drilled to guide the screws into place Replace the filters by sliding them into the plenum until they click into place INSTALLATION IS NOW COMPLETE PROCEED TO COMMISSIONING Fig 13 Shows the posit...

Page 10: ...rborne particles can pose a health risk particulalry to young children and the elderly Ensure that filters are cleaned in a safe and well ventilated area If a more thorough clean is required then the filters can be washed out using warm soapy water Care must be taken to avoid ripping the fabric The filters should be cleaned every two weeks or more when in use Prolonged use higher concentrations of...

Page 11: ... 4kg Model number 5860001 Electrical rating 240V 50Hz Refrigerant 407C 450g Rated capacity cooling 2000W heating 2150W Power input cooling 920W heating 930W Rated current cooling 3 9A heating 4 0A Max input 1020W Max current 4 4A Design system pressure hi 2900kPa low 1840kPa Max operating pressure 2400kPa Air delivery maximum 110l s Total installed weight 29kg ...

Page 12: ...ircommand service 7 5861006 Electrical kit 8 5862010 Inside fan assembly 9 5861002 Consensate collector set 10 5861001 Weather collar assembly 11 8001012 Circullar duct 12 8002031 Combined duct brace 13 8002037 Installation fittings kit 14 5852006 Sparrow plenum assembly 15 5601051 Remote control 16 8002044 Plenum filters pair 17 5603035 Louvre replacement set 6 per set Spare Parts ...

Page 13: ...13 Schematic Wiring Diagram ...

Page 14: ...the inside coil in heat mode On cooling the E5 will appear if the outside coil temperature exceeds 68O C This is an indication of condenser airflow reduced or non existent or condensor fan not working sufficiently or the thermistor is out of calibration NB When in heat mode at outside temperatures above 18O C the outside fan motors may cycle on and off This is the system shedding load to avoid ove...

Page 15: ...ssing the FAN button It is recommended that you choose AUTO Now select the desired ROOM TEMPERATURE herein referred to as SETPOINT by pressing the TEMP up or down buttons The readout will flash the setpoint temperature Keep pressing the button until it flashes your desired setpoint In approximately 5 seconds the display will resume reading the ACTUAL room temperature The compressor will have a del...

Page 16: ... com au For spare parts enquiries please email parts aircommand com au AIRCOMMAND EUROPE Locke Leisure Products The Gables Stoneleigh Road Bubbenhall Coventry CV8 3BT United Kingdom Phone 44 2476 303 380 AIRCOMMAND AUSTRALIA 954 Port Road Albert Park South Australia 5014 Australia Phone 61 8 8345 8444 Fax 61 8 8243 0628 Contact details ...

Reviews: