Airbloc ACR120HE12 Installation And Operating Manual Download Page 3

2  Air Curtain installation details

It is the sole responsibility of the installer to ensure that the points of
attachment to the building are sound.  Consultation with the consult-
ant/architect or owner of the building is recommended to ensure that
a sound, mechanically stable installation is achieved.

All attachments must be capable of supporting the weight of the
product detailed in Section 1.

Step 1

Before fitting or wiring the air curtain, ensure casing faces as above
and see general installation guidance notes.

Step 2

Step 3

Open the grille.  The grille is hinged to prevent the inner frame from
dropping.

Step 4

Attachment of the air curtain to the ceiling structure is by means of
the two brackets attached to the side of the air curtain.  The 
brackets may be removed to assist in passing the air curtain through
the recess then re-attached when in-situ.

Step 5

Either 10mm or 12mm drop rods or catenary wire (available from  
manufacturer) can be used to fasten the air curtain to the ceiling
support structure.

Note  When using drop rods the casing mounting brackets are slotted
and the mounting plates provided must be used on assembly.

Step 6

The height between the ceiling face and the face of the air 
curtain case needs to be adjusted to approximatley 40mm to enable
the grille assembly to fit flush with the ceiling.  Adjust accordingly.

ENSURE AIR OUTLET LOUVRES ARE NEAREST TO DOOR APPERTURE.

Access to the inside of
the air curtain grille can
be made by removing the
screws as indicated
below.

Outlet