CONDENSATE DRAINAGE
The models without a drain pump are equipped with condensate drain pipes.
Connect the drain system to the spigots.
2
3
4
5
6
7
min 3°
1
1 – drain pipe (Ø 20 mm) 2 – coupling 3 – L-shaped bend (Ø 20 mm) 4, 6 – connection pipe 5 – U-trap 7 – sewage system
A separate drainage system must be connected to each drain pipe. Connect the drain pipe, bend, U-trap and the sewage system with
metal, plastic or rubber connection pipes.
While laying the connection pipes provide the slope of minimum 3° downwards. Before starting operation, provide free drainage for the
condensed water, otherwise it is accumulated inside the unit that may cause the equipment damage and condensate outflow to the
room. Fill up the U-trap with water before using it.
For the units with a drain pump make sure that the flexible hose (Ø 6 mm) from the pump is connected to the sewage system.
The drain pump provides timely pumping of the condensed water from the unit.
THE CONDENSATE DRAINAGE SYSTEM IS DESIGNED FOR NORMAL OPERATION IN
PREMISES WITH AIR TEMPERATURES ABOVE 0 °C!
IF THE EXPECTED AMBIENT AIR TEMPERATURES ARE BELOW 0 °C, THE CONDENSATE
DRAINAGE SYSTEM MUST BE EQUIPPED WITH HEAT INSULATION AND PREHEATING
FACILITIES.