AIR SYSTEMS INTERNATIONAL SVF- 6ACAN Operating Manual Download Page 3

-4-

GENERAL SETUP & OPERATION

1.)

Place fan in a clean air environment.

2.)

Air quality of the confined space should be tested prior to ventilation.  If air quality of the
confined space is unacceptable, consult a trained professional.

3.)

Inspect fan for damaged or worn parts.  Inspect all ducting and couplings for air leaks prior
to fan operation.

4.)

Install duct cuff to exhaust flange and tighten cinch strap.  Keep bends and kinks in ducting
to a minimum to maximize air flow. If canister model is used, open lid and pull out ducting
and inspect for air leaks.

Note:  Maximum recommended duct hose length is 25 ft.

5.)

Set fan upwind from the work location and a minimum of 5 ft. from manhole.

6.)

Connect fan to power source.

DC versions require 12 VDC (attach red lead to the positive terminal, black lead to the
negative terminal on battery).  This unit must be run in the positive pressure mode as
this model is not approved for extracting (sucking) air. 

DO NOT REVERSE

WIRING.  

Warning:  Vehicular electrical systems must be able to handle 15

amp service or electrical damage may occur.

AC versions require 120 VAC, 15 amp, 60Hz service.

Note:  If an extension cord is required, the minimum recommended size
is 14 AWG  (0-25 ft.).  For further information, refer to the National Electric
Code Tables, Article 400.

7.)

Push on/off switch to “I” position.

TROUBLESHOOTING

PROBLEM

POSSIBLE CAUSE

SOLUTION

Excessive vibration Air intake blocked

Turn fan off and clear debris from intake

Possible internal damage

Turn fan off and inspect fan blades, shaft, and housing 
for debris, damage, and loose screws.                    

Note:  Never run fan for extended periods without 
installing duct on the exhaust flange. 

Possible external damage

Turn fan off and inspect

Fan will not start 

AC VERSION

Circuit breaker trips            

Wattage output insufficient                              
Extension cord improperly sized

Faulty wall outlet

Test voltage with meter

 

Faulty Capacitor

Check and replace. Order Part #ELCP75MFD               

Fan will not start 

DC VERSION

Blown Fuse (DC version only)   Check and replace.  Use only a 20A 32V fuse

Battery Connection

Ensure proper connection from battery clips to battery 
terminal posts          

Summary of Contents for SVF- 6ACAN

Page 1: ...25DCAN SVF 8ACUP Manual No BLWR02 Rev 9 April 2009 AIRSYSTEMSINTERNATIONAL INC 829 Juniper Crescent Chesapeake Va 23320 Telephone 757 424 3967 Toll Free 1 800 866 8100 Fax No 757 424 5348 http www ai...

Page 2: ...ric conditions can change rapidly Addi tional procedures and recommendations are available from federal state and local agencies DO NOT operate these fan units in a vertical position or with the flang...

Page 3: ...IRING Warning Vehicular electrical systems must be able to handle 15 amp service or electrical damage may occur AC versions require 120 VAC 15 amp 60Hz service Note If an extension cord is required th...

Page 4: ...7...

Page 5: ...nuamente mientras se ocupe el espacio limitado para asegurar una atm sfera estable y seguridad del trabajador ya que las condiciones atmosf ricas pueden cambiar r pidamente Procedimientos y recomendac...

Page 6: ...rios o pudiesen ocurrir da os el ctricos Las versiones de CA requieren un servicio de 120 VCA 15 amperios y 60 ciclos Nota Si se requiere un cord n el ctrico de extensi n el tama o m nimo recomenda do...

Page 7: ...lograr siete cambios de aire en el espacio limitado NOTAS ESPECIALES 1 La calidad del aire del espacio limitado deber a comprobarse antes de ventilarlo 2 Ventile el espacio limitado por el tiempo m ni...

Page 8: ...e confin pour assurer une atmosph re stable ainsi que la s curit du travailleur car les conditions atmosph riques peuvent changer rapidement Des proc dures et des recommandations sont disponibles aupr...

Page 9: ...ues peuvent se produire Les versions de courant alternatif n cessitent un service de 120 volts de courant alternatif 15 amps 60Hz Note si une corde d extension est n cessaire la dimension minimum reco...

Page 10: ...it de l air de l espace confin doit tre test e avant toute ventilation 2 Ventiler l espace confin pour les dur es minimums ainsi que d termin sur la charte ci dessus puis re tester l air 3 Si des gaze...

Page 11: ...BLE EL VENDEDOR EN CUANTO A P RDIDA DE INGRESOS CUALQUIER OTRO COSTO GASTO P RDIDA O DA O DIRECTO O INDIRECTO QUE OCURRA COMO RESULTADO DE DEFECTOS EN EL PRODUCTO O EN EL FALLO DEL PRODUCTO O CUALQUIE...

Reviews: