APPLICATION EXAMPLES

HOST POWER SUPPLY 

12 - 27.3VDC 

@ 56 - 79mA

TRIP POWER SUPPLY 

5 - 27.3VDC 

@ 2.0 - 17mA

Trip+ 
 T

rip-  Host+  Host -

NC    COM    NO      NC    COM    NO

YA

L

E

R  

02

3-

R

M

LOAD POWER SOURCE

120VAC

LOAD 

10A

LOAD 

7A

LOAD POWER SOURCE 

24VDC/VAC

MR-320 Dual Contact Voltage Example

NOTE: MR-310 WOULD PROVIDE 1 SET OF FORM

  “C” CONTACTS FOR A SINGLE LOAD

WHEN MR-320 RELAY COIL 

ENERGIZES, “NO” CONTACTS 

ARE SWITCHED TO CLOSED 

POSITION, SUPPLYING POWER 

TO TURN ON LOADS 

TTL 

BUILDING AUTOMATION 

COMPUTER DRIVER 

5VDC @ 2.5mA

Trip+ 
 T

rip-  Host+  Host -

YA

L

E

R  

01

3-

R

M

IDC

STYLE “B”

CLASS “B”

1

2

24VDC 

@42mA

MR-310 Typical TTL Driver Board to  Fire Alarm System Example

NC    COM    NO   

WITH MR-310 RELAY COIL 

ENERGIZED, MR-310 “NO” 

CONTACTS ARE CLOSED 

THUS ALARMING THE FACP

NOTE:FOR THIS APPLICATION 

         J1 IS INSTALLED (“IN”)

         J2 IS INSTALLED (“IN”)

           J3 IS REMOVED (“OUT”)

(Simultaneously switches 120VAC and 24VDC/VAC)

BOTH TRIP AND HOST INPUT 

VOLTAGES IN PROPER POLARITY 

ARE NEEDED TO ENERGIZE RELAY

UL

LISTED 

FACP

+

-

+

-

N

AC

+/AC

-/N

-/N

+/AC

N

AC

+

-

+
-

+

-

EOL

 RESISTOR

EOL 

RELAY

BOTH TRIP AND HOST INPUT 

VOLTAGES IN PROPER POLARITY 

ARE NEEDED TO ENERGIZE RELAY

MR-310 and MR-320 SERIES JUMPER CONFIGURATIONS

 © Air Products and Controls Inc. 2013   25 Corporate Drive   Auburn Hills, MI 48326   Ph. (248) 332-3900   Fax (248) 332-8807   www.ap-c.com

FOR ADDITIONAL APPLICATION INFORMATION AND/OR ASSISTANCE, 

PLEASE CONTACT OUR TECHNICAL SUPPORT HOTLINE. (888) 332-2241

(SUPERVISED BY FACP)

CAUTION:  DE-ENERGIZE ALL POWER BEFORE INSTALLATION OR SERVICE 

!

CAUTION:  DE-ENERGIZE POWER PRIOR TO REMOVING OR INSTALLING JUMPERS 

EOL RELAY “NO” CONTACT IS HELD 

CLOSED IN STANDBY ALLOWING 

FOR SUPERVISION BY FACP

MR-320 WOULD PROVIDE 2 SETS OF FORM 

“C”  CONTACTS TO SIMULTANEOUSLY 

ALARM THE FACP AND SWITCH A LOAD

NOTE:

(

(

NOTE:  INSTALLATION LIMITS UNDER JURISDICTION OF LOCAL AUTHORITY (NFPA STANDARDS 70, 72)

CSFM LISTED

RECOGNIZED COMPONENT

MEA ACCEPTED

INST APD0217 D140410 

Issue 1

MR-310 (SPDT) MR-320 (DPDT)

"A"                         

(LO trip -  HI host)

In

In

Out

Any

Maximum

5 - 18.4VDC

3.2 - 17mA 18.5 - 27.3VDC

"B"                              

(LO trip - HI host)

Out

In

Out

Resistive

Moderate

5 - 18.4VDC

2.5 - 13mA 18.5 - 27.3VDC

"C"                          

(HI trip - LO host)

In

Out

In

Any

Maximum

18.5 - 27.3VDC 2.1 - 3.3mA 12 - 18.4VDC

"D"                             

(HI trip - LO host

Out

Out

In

Resistive

Moderate

18.5 - 27.3VDC 2.0 - 3.2mA 12 - 18.4VDC

"E"                         

(LO trip - LO host)

In

In

In

Any

Maximum

5 - 18.4VDC

3.2 - 17mA 12 - 18.4VDC

"F"                           

(LO trip - LO host)

Out

In

In

Resistive

Moderate

5 - 18.4VDC

2.5 - 13mA 12 - 18.4VDC

"G"                          

(HI trip -    HI host)

In

Out

Out

Any

Maximum

18.5 - 27.3VDC 2.1 - 3.3mA 18.5 - 27.3VDC

"H"                          

As Shipped            

(HI trip -    HI host)

Out

Out

Out

Resistive

Moderate

18.5 - 27.3VDC 2.0 - 3.2mA 18.5 - 27.3VDC

36 - 40mA

69 - 73mA

38 - 46mA

56 - 79mA

36 - 40mA

69 - 73mA

Current

Voltage

Current

38 - 46mA

56 - 79mA

Voltage

J1 (Load)

Modes 

(Application)

Host Input

Application Configuration

Load Type

Inductive Load 

Breaking Power

J3 (Host)

J2 (Trip)

Trip Input

ATTENTION: TENSION TOUS PUISSANCE AVANT L'INSTALLATION OU SERVICE

ATTENTION: DE-ENERGIZE ALIMENTATION AVANT DE RETIRER OU D'INSTALLER CAVALIERS

LIMITES D'INSTALLATION SOUS RESPONSABILITÉ DES COLLECTIVITES LOCALES (normes de la NFPA 70, 72): REMARQUE