Installation Instructions
Wiring Instructions
1. The Bi-Polar 2400 is internally fused; external or in-line fuses are not required.
Check with your local electric codes and follow all guidelines.
2. Review the model number found on the Bi-Polar 2400 product and wire it only to
the voltage range shown below. Disconnect power to the air handler the Bi-Polar
2400 will be mounted to during installation.
3. If connecting to a 24VAC power source with a grounded transformer leg, con-
nect the grounded leg to the black wire.
4. Unit can be powered 24/7 or it may be interlocked to cycle with blower.
5. Green light will illuminate when powered and operating correctly.
Black wire: Neutral or Ground
Red wire: Positive Input
3 Models:
BP2400-24 Usage
24 VAC / 400mA
BP2400-110 Usage
110-120 VAC / 80mA
BP2400-220 Usage
208-277 VAC / 40mA
Preparing to Install Your New Bi-Polar
®
2400 unit
The Bi-Polar
®
was designed to be simple and effective. Remove the unit & mount-
ing hardware (two self tapping screws) from the box. We recommend keeping
the box and all packaging material for shipping the unit, should it ever need to be
returned for repairs. Locate the ideal location within the air stream. We recommend
after a prefilter but before the cooling coil. Alternately, it can be mounted in the
supply air.
Caution
Installation and servicing of air-conditioning equipment can be hazardous due to
system pressure and electrical components. Only trained and qualified service
personnel should install, repair, or service air-conditioning equipment. Air Oasis
and its affiliates are not responsible for any damage to the Bi-Polar
®
unit, or injury
to yourself or others, if you elect to install the device without utilizing qualified
technicians.
Use the suggestions on page 3 to determine the optimal mounting location(s).
To complete the installation process you will need the following tools:
• 1/4 inch hex head screw driver
Should be installed with brushes a minimum of 1 to 2 inches away from any
metal and where the air can easily flow through the brushes.
Installation Instructions