background image

NOTE:

 If the housing is mounted too far or not far enough into the ceiling for the flange to 

make a solid connection, loosen the mounting channel and adjust the housing up or down on 

the rails. Once in place, fully tighten the mounting channel nuts.
5a. 

STANDARD AND HUMIDITY SENSING MODELS: 

Install the grill by squeezing the two 

ends of the springs together and installing them up into the slots on the fan’s housing. 

Push the grill up into position 

(Figure 12).

5b. 

MOTION SENSING MODELS: 

Install the grill by squeezing the spring furthest from 

the motion sensor together and installing it up into the slot furthest from the wire 

compartment on the fan’s housing. Attach the 3 pin quick connect from the motion sensor 

on the grill to the wire compartment

.

 This cord will only fit one way into the receptacle. 

Install the other spring in place and push the grill up into position 

(Figure 13).

6. 

Restore power and test your installation.

SECTION 7

Programming the Occupancy Sensor

1a. 

Setting the Occupancy Time Delay.

 This will set the amount 

of time the fan will continue to operate after the room is 

vacated. Locate the motion sensor on the fan’s grill and press 

the button 2 times. The LED on the sensor will then flash the 

number of times to indicate the current setting, this will repeat 

3 times:

 

 

1 time = 30 seconds 

 

 

2 times = 2.5 minutes  6 times = 12.5 minutes

 

 

3 times = 5 minutes   7 times = 15 minutes 

 

 

4 times = 7.5 minutes   8 times = 17.5 minutes

 

 

5 times = 10 minutes   9 times = 20 minutes

1b.  To adjust the setting, while the sensor is still flashing from 

Step 1a

, press the button the 

number of times that corresponds with the amount of time you desire, for instance 3 times 

www.airkinglimited.com

6727900 Rev. D 9-16

4 of 12

sets the delay to 5 minutes (see numbers in 

Step 1

). The sensor will then flash the number 

of times for the new setting 3 times before exiting back to the programming mode.

2a 

Setting the Minimum On Time.

 This sets the minimum time the fan will operate once 

motion is detected within the room. This works in conjunction with the Occupancy Time 

Delay feature set in 

Steps 1a

 and 

1b

. For instance if you set the minimum time on for 15 

minutes and the Time Delay for 5 minutes, the fan will operate for at least 15 minutes 

then 5 additional minutes.

 

NOTE:

 This is a minimum time that the fan will operate. If the room is occupied longer, the 

fan will continue to run until the room is vacated and the occupancy time delay has elapsed.

2b.  Locate the motion sensor on the fan’s grill and press the button 10 times. The LED on 

the sensor will then flash the number of times to indicate the current setting, this will 

repeat 3 times:

 

 

1 time = 0 minutes 

 

4 times = 45 minutes

 

 

2 times = 15 minutes   

5 times = 60 minutes

 

 

3 times = 30 minutes

2c.  To adjust the setting, while the sensor is still flashing from 

Step 2b

, press the button 

the number of times that corresponds with the amount of time you desire, for instance 

3 times sets the minimum on time to 30 minutes (see numbers in 

Step 2b

). The sensor 

will then flash the number of times for the new setting 3 times before exiting back to the 

programming mode.

3.  Once all setting have been made and the sensor will return to detection mode and the 

LED will flash when occupancy of the room is detected.

SECTION 8

Setting the Humidistat

This fan may be equipped with a humidity sensor that automatically turns the fan on when 

humidity is above set point and off when humidity is at or below set point. If the fan is operating 

too long or not enough, first check to see the humidity sensor set point. In cases where the 

ambient humidity level of the room rises higher than the preset level, the fan will turn on even if 

the room is not occupied. This helps prevent conditions that lead to mold growth.

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE SERVICING THE UNIT.

1. 

To set the desired humidity level of the room, remove the grill and locate the 

dehumidistat dial located on the wire compartment cover. 

2. 

Set the dial to the relative humidity you want the fan to maintain usually between 50% & 

80%. Moist climates will require higher settings than dry climates. When the humidity level 

of the room is below this setting the fan will remain off. When the humidity level rises about 

this setting the fan will turn on and run until the humidity level falls below this setting. 

3. 

Reinstall the grill and restore power. 

SECTION 9

Setting the Speed

This unit features a variable speed function that allows it to be set from 30 to 130 CFM. To 

adjust the airflow:
1. 

Remove the grill and find the adjustment post on the top of the wire compartment.

2. 

Turn the post to the desired CFM setting then reinstall the grill.

NOTE:

 The motor will adjust to the static pressure of the installation to maintain the desired 

CFM. For higher speeds / higher static pressure installations, airflow testing may be required 

to insure the proper amount of ventilation.

SECTION 10

Use and Care

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE SERVICING THE UNIT.

1. 

Cleaning the Grill:

 Remove grill and use a mild detergent, such as dishwashing liquid, 

and dry with a soft cloth. NEVER USE ANY ABRASIVE PADS OR SCOURING POWDERS. 

Completely dry grill before reinstalling. Refer to instructions in 

Section 6

 

Completing the 

Installation

, to reinstall grill.

2. 

Cleaning the Fan Assembly:

 Wipe all parts with a dry cloth or gently vacuum the fan. 

NEVER IMMERSE ELECTRICAL PARTS IN WATER.

Fuse

1. 

Follow the steps in 

SECTION 5

 

Wiring

 to gain access to the 

fuse holder located inside the wire compartment. To replace 

the fuse, squeeze the top an bottom of the fuse holder together 

while twisting the larger piece in a direction away from the 

tabs 

(Figure 14)

. Replace fuse only with 0.5 Amp, 250VAC, 5 x 

20mm, Fast Acting fuse. Reconnect the fuse holder by lining up 

the top an bottom section and squeeze together while twisting 

until they are locked in place. Carefully tuck back into the wire 

compartment and reinstall the wire compartment cover.

Figure 12

Figure 13

Figure 11

Screws

Ceiling 

Mounting 

Flange

Screw Holes

Figure 14

Summary of Contents for D4S

Page 1: ...ent air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code auth...

Page 2: ...the previously cut hole so that it is flush with the finished ceiling Secure the ends of the rails to the joists Figure 1 www airkinglimited com 6727900 Rev D 9 16 2 of 12 SECTION 4 Ducting NOTE 6 OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE CAUTION ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL BUILDING CODES NOTE The ducting from this fan to the outside of the building has a strong ...

Page 3: ... to the green wire from the fan housing Figure 9 Use approved methods for all connections NOTE The yellow wire may contain a wire crimp nut which will have to be cut off and the wire stripped 4 Carefully tuck wire back inside wire compartment and replace wire compartment cover securing with the screw that was removed earlier SECTION 6 Completing the Installation 1 Use a sealant appropriate for con...

Page 4: ...nimum on time to 30 minutes see numbers in Step 2b The sensor will then flash the number of times for the new setting 3 times before exiting back to the programming mode 3 Once all setting have been made and the sensor will return to detection mode and the LED will flash when occupancy of the room is detected SECTION 8 Setting the Humidistat This fan may be equipped with a humidity sensor that aut...

Page 5: ... does not apply if the product was damaged or failed because of accident improper handling or operation shipping damage abuse misuse unauthorized repairs made or attempted This warranty does not cover shipping costs for the return of products to Air King for repair or replacement Air King will pay return shipping charges from Air King following warranty repairs or replacement ANY AND ALL WARRANTIE...

Page 6: ...acement Part 7 1 Grill 5S1202048 8 1 Wire Compartment Assembly 5S1250103 Specific to Model D4SG Qty Description Replacement Part 9 1 Wire Compartment Assembly 5S1250114 15 1 Grill Assembly 5S1239115 Specific to Model D4SH Qty Description Replacement Part 7 1 Grill 5S1202048 10 1 Wire Compartment Assembly 5S1250115 13 1 Knob 5S1299802 14 1 Humidity Sensor Compartment 5S1239826 Specific to Models D4...

Page 7: ...uit cheminée provenant d équipement de brûlage au combustible pour prévenir un refoulement Suivre les directives du fabricant de l équipement de chauffage et les normes de sécurité telles que celles publiées par la National Fire Protection Association NFPA et de la American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE et de celles des autorités locales du code c Lors de ...

Page 8: ...es rails aux solives Figure 1 www airkinglimited com 6727900 Rev D 9 16 8 of 12 SECTION 4 Conduits NOTE UN CONDUIT PLUS RIGIDE DE 6 PO OU PLUS EST RECOMMANDE POUR UNE MEILLEURE PERFORMANCE ATTENTION TOUS LES CONDUITS DOIVENT ÊTRE CONFORMES AUX CODES DU BÂTIMENT LOCAUX ET NATIONAUX REMARQUE La canalisation de ce ventilateur à l extérieur du bâtiment a un effet important sur le flux d air le bruit e...

Page 9: ...ectez le fil de la position automatique sur l interrupteur mural au fil noir du ventilateur connectez le fil de la position manuelle sur l interrupteur au fil jaune du ventilateur Connectez le fil de terre de la maison au fil vert du boîtier du ventilateur Figure 9 Utiliser des méthodes approuvées pour toutes les connexions REMARQUE Le fil jaune peut contenir un écrou de fil à sertir qui devra êtr...

Page 10: ...de mouvement sur le gril du ventilateur et appuyez sur le bouton 10 fois Le LED sur le capteur clignote alors le nombre de fois pour indiquer le réglage actuel Ceci sera répété 3 fois 1 fois 0 minutes 4 fois 45 minutes 2 fois 15 minutes 5 fois 60 minutes 3 fois 30 minutes 2c Pour ajuster le réglage tandis que le capteur est continue de clignoter de l étape 2b appuyez sur le bouton le nombre de foi...

Page 11: ...te garantie ne couvre pas les coûts d expédition pour le retour des produits à Air King pour la réparation ou le remplacement Air King payera les frais d expédition de retour de Air King après les réparations ou le remplacement de garantie TOUTES LES GARANTIES EXPRESSES OU TACITES COMPRENANT SANS LIMITATION TOUTE GARANTIE TACITE DE VALEUR MARCHANDE DURENT UN AN DE LA DATE DE L ACHAT ORIGINAL OU JU...

Page 12: ... 5S1202048 8 1 Assemblée du compartiment du fil 5S1250103 Particularités de modèle D4SG Qté Description de pièce de remplacement 9 1 Assemblée du compartiment du fil 5S1250114 15 1 Assemblée de Grille 5S1239115 Particularités de modèle D4SH Qté Description de pièce de remplacement 7 1 Grille 5S1202048 10 1 Assemblée du compartiment du fil 5S1250115 13 1 Bouton 5S1299802 14 1 Compartiment du capteu...

Reviews: