67
12
×
★
Ο
★
Outdoor
ambient
temperature
too low
protection
Outdoor ambient temperature
too low
13
★
×
Ο
×
Compressor
exhaust
temperature
too high
protection
a.
the compressor exhaust
temperature sensor is failure;
b.
the refrigerant of the unit is
not enough
14
★
×
Ο
★
Outdoor
ambient
temperature
sensor in
trouble
a.
the outdoor ambient temperature
sensor connect loose;
b.
the outdoor ambient temperature
sensor is failure;
c.
the outdoor control board is
failure
15
★
★
Ο
×
Compressor
shell
temperature
too high
protection
a.
the compressor exhaust
temperature sensor connect loose
b.
the refrigerant of the unit is
not enough
16
Anti-freeze
protection with
cooling or
overload
protection with
heating in
a.
the indoor coil temperature
sensor connect loose;
b.
the indoor coil temperature
sensor is
failure;
c.
t
he indoor control board is failure
d.
the refrigerant system is
abnormal.
17
PFC
protection
a.
the PFC is failure;
b.
the outdoor drive board is
failure
18
DC
compressor
start failure
a.
the outdoor drive board is
failure;
b.
the compressor is failure
19
×
×
×
Ο
Compressor
drive in trouble
a.
the outdoor drive board is
failure;
b.
the compressor is failure
c.
the outdoor control board is