Aiphone LEF-3L Instructions Manual Download Page 12

– 12 –

TROUBLESHOOTING GUIDE (Cont.)

ENTRY #  PROBLEM

POSSIBLE CAUSE

SOLUTION

5

No master-to-master 

communication. 

C  terminals mis-wired 

between masters.

Communication between masters is carried on the # wire of the calling 

master to the  C  terminal of the receiving master. Verify that the  C  terminal 
of the master that is being called is actually wired to the #terminal that is 

being selected on the calling master.

6

LEF master has no 

communication or tone, but 

LED lights work. 

Wrong power supply is 

being used. 

The LED lights will operate with a power source from 6VDC - 24VDC. The 

amplifi er in the LEF unit will only work when the system is supplied 12VDC. 

Proper power supply is the PS-1225/UL/S, or PS-1215 DIN.

7

Feedback when the volume 

control is turned up over 

halfway.

E  /  —  jumpers attached 

in a multi-master system.

Remove  E   /  —   jumpers on masters and door stations in the system, 
provided there are 3 wires to the sub(s). If the sub only has 2 wires in a 

multi-master system, the jumper must remain in place for the door call-in to 

work. In this case, the side effect is the feedback problem when the audio 

volume is turned up. The only alternative is to run the proper wire to the 

door station(s) and remove all of the jumpers.

8

New installation has AC 

buzz, noise, or hum in 

system.

Too close to AC and/or 

incorrect wire was used.

If the units are too close to an AC source such as AC wiring or dimmer 

switches, move the intercom at least one stud space away from the AC 

source. Other precautions include using shielded cable. If shielded wire was 

used and there is still AC noise, tie all the shields together and ground to 

an earth ground or negative on the power supply. If more than one jacketed 

cable was used between masters, make sure the # terminals,  C   terminal, 

and the  E   terminals are all in the same jacketed cable. If multiple cables 

were used, include an  E   wire in each cable that carries a station number 
wire in it.

9

Door release does not work. 

Miswire or lack of RY-PA 

relays.

Check the  WHITE   wire coming out of the PC board for voltage. When 

depressing the Door release ( 

 ) button, 12VDC is present across  WHITE  

and  — , which activates the relay. Ensure that the  BLACK   wires of the 
RY-PA are connected to  WHITE   and either the  BROWN ,  RED , or 

ORANGE  wire for selective door release (which provides selective ground 

when the corresponding channel is selected).

10

No call tone between 

masters.

No Privacy feature on LEF-

3L. 

Features not available

The LEF-3L unit does not have the PRIVACY feature or the ability to send 

a call tone to another master station (as with the standard LEF-3). This 

function is removed to allow the switch to be used for door release instead 

of privacy.

11

Can't release the door from 

the 2nd (additional masters) 

Wiring not connected 

properly. 

If door release works from the fi rst master but not another(s), verify that 

selective door release wires are connected between masters. ( WHITE , 

BROWN ,  RED ,  ORANGE ). RY-PA's are only required at one master.

12

External Signaling device 

doesn't activate

RY-AC mis-wired

Make sure that the WHITE wire of the RY-AC is connected to the # 

terminal that is to be activating the relay, and that  RED  and  BLACK  are 

connected to 

+

 and  — , respectively.

WARRANTY

Aiphone warrants its products to be free from defects of material and workmanship under normal use and service for a period of one year after 
delivery to the ultimate user and will repair free of charge or replace at no charge, should it become defective upon which examination shall 
disclose to be defective and under warranty. Aiphone reserves unto itself the sole right to make the fi nal decision whether there is a defect in 
materials and/or workmanship; and whether or not the product is within the warranty.
This warranty shall not apply to any Aiphone product which has been subject to misuse, neglect, accident, or to use in violation of instructions 
furnished, nor extended to units which have been repaired or altered outside of the factory. This warranty does not cover batteries or damage 
caused by batteries used in connection with the product.
This warranty covers bench repairs only, and any repairs must be made at the shop or place designated in writing by Aiphone. Aiphone will not be 
responsible for any costs incurred involving on site service calls.

AIPHONE CO., LTD., NAGOYA, JAPAN
AIPHONE CORPORATION, BELLEVUE, WA, USA
AIPHONE S.A.S., LISSES-EVRY, FRANCE

http://www.aiphone.com/

Printed in Japan (E)

aiphone̲e.indd   12

09.2.17, 2:14:25 PM

Summary of Contents for LEF-3L

Page 1: ...result 2 When mounting the unit on wall install the unit in a convenient location but not where it could be jarred or bumped Injury could result 3 For DC powered systems use Aiphone power supply model specified with system If non specified product is used fire or malfunction could result 4 Do not install or make any wire terminations while power supply is plugged in It can cause electrical shock o...

Page 2: ...ce or flush mount with or without privacy LE A LE AN LE B LE BN Weather resistant door stations LE D LE DA LE DL Vandal proof sub stations LE SS LE SSR LS NVP C Subs call in with momentary tone and LED remaining lit for approximately 20 seconds Selective calling to sub stations Selectively control external device from the master station in one of two ways with relay Momentary closure while Door re...

Page 3: ...V DC 1 5A power supply use for intercom only 1 per system LEF 3L TERMINAL DEFINITIONS Positive 12V DC Negative E Common communication 1 3 Station number communication to sub or other master C CALL for receiving a call from another master station R Occupied light control 0V DC when system is occupied COLOR CODED WIRES White Common Door release activation 12V DC when door release button is pressed B...

Page 4: ...ion numbers for all sub station locations Surge protection for the intercom equipment is recommended Add SA 1 surge arrestors for the power supply plus one per two wires connected to the master station Any other manufacturer s products installed with this system power supply external signaling device etc are not covered under Aiphone s warranty When using a power supply that has no GROUND terminal...

Page 5: ...the master station Intercom Locations Do not install intercoms near dimmer or light switches or other electrical wall devices To prevent feedback do not place sub stations back to back on a common wall Near alarm panels or other electronic equipment that may emit data noise Behind a doorway or any other area that may block access to the unit Before actually installing the LEF system Precautions on...

Page 6: ...ster is in occupied mode No call tone between masters Cable requirements Use multi conductor cable with an overall shield non twisted 22AWG to 18AWG 0 65mm to 1 0mm to accommodate the maximum number stations in the system Use the gauge specified for the maximum distance between the two farthest stations Power supply The entire LEF system can be powered by one power supply PS 1225UL PS 1225S 12VDC ...

Page 7: ...on OFF button standby Voice vol Control Occupied LED TALK button Door release LED Operation plate Back wiring LE room subs Surface wiring or Desk top use 1 2 When running cable on the surface pass cable through the top or bottom of the chassis and fasten with the wire clamps attached one outside and one inside chassis To pass the cable through the bottom side of the unit cut out the cable inlet se...

Page 8: ...n AContact Rating AC110V 1A DC24V 1A To prevent shorts be sure to cut unused lead wires at the button and insulate the ends To prevent shorts be sure to cut unused lead wires at the button and insulate the ends E 1 Green Black Red 3 2 C 1 E LEF 3L PS 1225 UL S PS 1215DIN 12V DC POWER ONLY LEF 3L RY PA AC Transformer A R Y 3 C 1 2 E R Y E LE D LE DA LS NVP LE SS LEF 3L Black Yellow White Brown Red ...

Page 9: ...ires at the button and insulate the ends AContact Rating AC110V 1A DC24V 1A Contact Rating 0 3A 240V AC 1 0A 24V DC To prevent shorts be sure to cut unused lead wires at the button and insulate the ends 3 2 C 1 E LEF 3L PS 1225 UL S PS 1215DIN 12V DC POWER ONLY LEF 3L AC Transformer A LE D LE DA 3 C 1 2 E R Y R Y RY PA 1 E RY AC AC Transformer External Sounder Black Black Red White Yellow Yellow W...

Page 10: ...n LEF 3L provides selective door release to multiple doors One RY PA for each door When communication is established to a door station press the Door release button to release the corresponding door strike Camera Call up feature If the Camera Call up feature is included the associated relay will provide a maintained closure as long as the station is selected at the master NOTE The LEF 3L does not ...

Page 11: ...e master station Replace jumper In a multi master system the E jumper should be removed and 3 wires should be connected 2 Door station does not call in no call tone or LED light 3 wire connection Missing connection of terminal If communication works check connection between terminal of door station and master Test call in at master station by touching a jumper wire between and terminal of master I...

Page 12: ...oss WHITE and which activates the relay Ensure that the BLACK wires of the RY PA are connected to WHITE and either the BROWN RED or ORANGE wire for selective door release which provides selective ground when the corresponding channel is selected 10 No call tone between masters No Privacy feature on LEF 3L Features not available The LEF 3L unit does not have the PRIVACY feature or the ability to se...