Aico Ei100R Manual Download Page 8

maximum recommended cable resistance is 20 ohms. All
wiring must comply with local codes. Screw unit to ceiling
using screws provided. Put cover back on the Smoke Alarm
by matching up hinges and gently snapping it on to the base.

Caution:

(a) The Smoke/Heat  Alarm must be wired to a 12V supply
that is permanently on.

(b) Positive air pressure at wiring openings, conduit or
mounting boxes/holes can cause draughts through and away
from the Smoke/Heat Alarm which may prevent correct
operation. Any such openings must be sealed (with silicone
rubber or similar) to prevent unwanted air movement.

Interconnecting Smoke Alarms and Heat Alarms

When a fire is sensed the alarm must be given throughout the
house. Up to twelve (12) Smoke Alarms (models Ei100R3,
Ei105R3 & Ei105R4 only) and Heat Alarms (model Ei103R
only) can be interconnected so that when one senses fire all
alarm. Do not interconnect to any other type of alarm. The unit
initiating the alarm can be identified by its LED flashing every
second. Figure 6 shows the interconnect wiring.

These Alarms should be interconnected only within the
confines of a single family living unit. If they are
interconnected between different units there may be
excessive nuisance alarms. Everybody may not be aware that
they are being tested or that it is a nuisance alarm caused by
cooking etc.

8

13425-R1-12V COMMON-UC  29/9/09  7:56 AM  Page 8

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Ei100R

Page 1: ...ALARM UNTIL ALL BUILDING WORK IS COMPLETED TO AVOID CONTAMINATION AFTER CHECKING OPERATION COVER SMOKE ALARM WITH DUST COVER UNTIL REQUIRED FOR USE LOCATE IONISATION ALARMS Ei100R3 AWAY FROM KITCHENS...

Page 2: ...g is given For maximum protection you should put individual Smoke Alarms in all the rooms where fire is most likely to break out apart from kitchens bathrooms garages see Locations to Avoid A Smoke Al...

Page 3: ...out from a room is often cool and slow moving so it can take a long time to rise to the ceiling and travel to a detector which could be some distance away A Heat Alarm in the closed room will give ea...

Page 4: ...ot be sufficient This is because no matter where it is located it will be more than 7 5 metres from potential fires In houses with more than one sleeping area Smoke Alarms should be placed between eac...

Page 5: ...re that it wouldn t wake a person If a Smoke Alarm is too far away for it to wake a person it is best to interconnect it to another Smoke Alarm or Heat Alarm near the bedroom The following alarms Ei10...

Page 6: ...detector chamber can cause intermittent alarms Insects and contamination on the Heat Alarm sensor can increase its response time POSITIONING SMOKE HEAT ALARMS The location must comply with applicable...

Page 7: ...when appropriate Excessive dust and debris from building work can contaminate the smoke chamber and cause problems it will also invalidate the guarantee If it must be installed cover it completely pa...

Page 8: ...arms and Heat Alarms When a fire is sensed the alarm must be given throughout the house Up to twelve 12 Smoke Alarms models Ei100R3 Ei105R3 Ei105R4 only and Heat Alarms model Ei103R only can be interc...

Page 9: ...every second while horn is sounding The alarm will stop when the button is released Pressing the test button simulates the effect of smoke heat during a real fire and is the best way to ensure the Al...

Page 10: ...the Ei100R3 Ionisation alarm due to cooking fumes you could consider replacing it with an Optical Alarm Ei105R3 or Ei105R4 as they are significantly less susceptible to cooking fumes If you experienc...

Page 11: ...e not a substitute for insurance The supplier or manufacturer is not your insurer The chamber inside the Ionisation Ei100R3 Smoke Alarm contains a small amount of radioactive material 33kBq of Americi...

Page 12: ...Smoke Heat Alarms have significantly helped to reduce the number of fire fatalities in countries where they are widely installed However independent authorities have stated that they may be ineffecti...

Page 13: ...Alarm Optical or Ion Both types respond in all standard fires but each type may respond faster to particular fires as shown The EI company manufactures complementary 12 Volt Smoke Alarms Optical Smoke...

Page 14: ...Am241 Airspeed No false alarms up to 22mph 10M s Button Test Simulates the effect of smoke and checks chamber electronics and horn Ei105R3 Ei105R4 Sensor Optical uses light scatter from smoke Sensitiv...

Page 15: ...i100R3 140 x 125 x 46 mm Ei105R3 140 x 125 x 46 mm Ei105R4 140 x 125 x 46 mm Ei103R 140 x 125 x 58 mm Weight 170 grams 6 oz Specifications are subject to change TROUBLESHOOTING ALARM SOUNDS FOR NO APP...

Reviews: