I-41
A-070336_EN • Rev. A
P
roduct
I
nstallatIon
Item
From
(Main board)
Terminal No
To
Terminals
Remark
On/Off switch
X1a (A1)
1(N), 2 (PE),
3 (L)
Rear Box (RB)
1 (PE), 2 (N) &
3 (L)
Heating Circuit pump/
DHW pump (opt)
X1b (QX) - QX2 2 (N) & 1 (L)
Rear Box (RB)
13 (N) & 14 (L)
Heating Circuit pump/
Flue gas damper (opt)
X1b (QX) - QX3
4 (N) & 5 (L)
Rear Box (RB)
10 (N) & 11(L)
Boiler pump
X1f (C1) - QX1
2 (N) & 1 (L)
Rear Box (RB)
7 (N) & 8 (L)
Fan
X1f (C1) - AC
Fan
7 (N) & 6 (L)
item (C4)
L & N
Fan PWM
X8 (J1) - Fan
PWM
1 (GND), 2, 3
& 4
item (J2)
GND, +24V,
HALL, PWM
Safety water temp. switch
X18 (D1)
1 & 2
item (D2)
230 V
Ignition transformer
X2 (E1)
3 (L) & 4 (N)
item (E3)
L & N
Gas valve
X2 (E1)
1 (L) & 2 (N)
item (E2)
L & N
Ionization electrode
X3 (T1)
item (T2)
Gas pressure switch
X5a (H1) - H6
1 (S) & 2 (GND) item (Z1)
2 (S) & 3 (GND)
System temp sensor / Multif.
X5a (H1) - BX1
3 (S) & 4 (GND) Front panel 1 (FP1) - BX1
(Z2)
1 (S) & 2 (GND)
Cascade return temp sensor
(opt) / Multif.
X5a (H1) - BX2
5 (S) & 6 (GND) Front panel 1 (FP1) - BX2 (Z3) 9 (S) & 10 (GND)
Flue gas sensor
X5a (H1) - BX3
7 (S) & 8 (GND) item (H3)
DHW sensor (opt)
X5a (H1) - B38
9 (S) & 10
(GND)
Front panel 1 (FP1) - B38 (Z4) 3 (S) & 4 (GND)
Optional item
Outside temperature sensor
(opt)
X5a (H1) - B9
11 (S) & 12
(GND)
Front panel 1 (FP1) - B9 (H5) 5 (S) & 6 (GND)
Optional item
Enable/Disable - multifunc-
tional
X6a (L1) - H1
1 (S) & 2 (GND) Front panel 1 (FP1) - H1 (L4) 7 (S) & 8 (GND)
Door temp. limit switch
X6a (L1) - H4
5 (S) & 6 (GND) item (L3)
Condensate level switch
X6a (L1) - H5
7 (S) & 8 (GND) item (L2)
Analog output /0-10V (opt)
X10a (K9) - UX2 1 (S) & 2 (GND) Front panel 1 (FP1) - UX2 (K8) 13 (S) & 14 (GND) Optional item
Analog output / 0-10V (opt)
X10a (K9) - UX3 3 (S) & 4 (GND) Front panel 1 (FP1) - UX3 (K7) 15 (S) & 16 (GND) Optional item
Cascading module (opt)
X11
Optional item, refer to
“Optional Modules” on page I-53
Air pressure switch (opt)
X4 (I1) - H7
2 (S) & 7 (GND) item (I8)
Optional item
Safety water pressure sensor
X4 (I1) - H3
3 (S) & 7 (GND) item (I3)
Ground through terminal 7
Return circuit sensor
X4 (I1) - BX4-B7 6 (S) & 7 (GND) item (I2)
Supply circuit sensor
X4 (I1) - B2
8 (S) & 7 (GND) item (I4)
Display Unit
X50
item
Connected through cable Hub, which is used
for optional modules (refer to
P1 PWM
X15 (U1)
2 (S) & 1 (GND) Front panel 1 (FP1) - X15 (U2) 11 (S) & 12 (GND)
Web Server (opt)
X16 (I5)
1 (S)
Front panel 1 (FP1) - (W1)
17 (S) & 18 (GND) Optional item
X4 (I1)
7 (GND)
The electronic board is protected by 2 fuses (T6.3AH 250V)