electronic device Secop GP 105N4627 

 
 

1  Purpose 

In this procdeure we describe the task to control the released Setup values which are programmed 
into the Secop GP electronic device  

 

2  Area of Application 

Is relevant for all divisions which are working with the Secop GP electronic controller 

3  Terms 

4  Responsibility 

Contents 

5.1

 

Setups for Cabinets with Plastic Tank ...................................................................... 3

 

5.1.1

 

Setups for Cabinets with AD Function and with Buzzer ..................................... 3

 

5.1.2

 

Setups for Cabinets with AD Function and without Buzzer ................................ 4

 

5.2

 

Setups for Cabinets with ALU Tank ....................................................................... 10

 

5.2.1

 

Setups for Cabinets with AD Function and with Buzzer ................................... 10

 

5.2.2

 

Setups for Cabinets with AD Function and without Buzzer .............................. 11

 

5.2.3

 

Setups for Cabinets without AD Function and with Buzzer .............................. 17

 

5.2.4

 

Setups for Cabinets without AD Function and without Buzzer ......................... 18

 

 

Summary of Contents for Secop GP 105N4627

Page 1: ... Application Is relevant for all divisions which are working with the Secop GP electronic controller 3 Terms 4 Responsibility Contents 5 1 Setups for Cabinets with Plastic Tank 3 5 1 1 Setups for Cabinets with AD Function and with Buzzer 3 5 1 2 Setups for Cabinets with AD Function and without Buzzer 4 5 2 Setups for Cabinets with ALU Tank 10 5 2 1 Setups for Cabinets with AD Function and with Buz...

Page 2: ...bus address can be adjusted between 1 and 247 4 step To store the bus address press the man defrost key once to quit the address menu and get back to the current temperature 5 step To get into the main menu press the key three times to get to the code input for the main menu Cod and 0 are displayed The correct code should be entered using the key up or standby reset down The code can be a number b...

Page 3: ...8 t45 t46 t47 L03 r15 r01 o17 r4 r5 MIAMI 185 ECO L AD VS KSW LIDL A1 with buzzer 221670 A1 16 50 50 A1 on off off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 25 50 0 C MIAMI 210 250 ECO AD VS KSW LIDL A1 with buzzer 221671 A1 16 50 50 A1 on off off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 24 50 0 C 16 50 50 A1 on off on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 25 50 0 C 5 5 100 A3 on off on off off ...

Page 4: ...P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 40 A1 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 26 40 0 C 16 50 40 A2 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 28 40 0 C Ibiza 100 145 L AD VS A D CH Unilever EU AHT 209962 A1 16 50 40 A1 on off off off off on 8 50 0 3 1 1 1 1 1 1 1 1 1 40 24 40 0 C 16 50 50 A1 on on off ...

Page 5: ...10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 50 A1 on on on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 26 50 0 C 16 50 50 A2 on on on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 28 50 0 C 5 5 100 A3 on on on off off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C Athen ECO 175 210 AD VS KSW D Norma 221361 A1 16 50 50 A1 on off off of...

Page 6: ...5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C 9 1 40 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 40 4 40 0 C 16 50 50 A1 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 25 50 0 C 16 50 50 A2 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 27 50 0 C 16 50 50 A1 on on on on off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 25 50 0 C 16 50 50 A2 on on on on off on 8 70 0 3 1 1 ...

Page 7: ... 1 1 1 1 1 40 26 40 0 C 5 5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C 9 1 40 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 40 4 40 0 C 16 50 50 A1 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 26 50 0 C 16 50 50 A2 on on off off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 28 50 0 C 16 50 50 A1 on on on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 26 50 0 C 16 50 50 A2 on on...

Page 8: ...7 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 40 A1 on on on on off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 26 40 0 C 16 50 40 A2 on on on on off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 28 40 0 C 5 5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C 9 1 40 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 40 4 40 0 C 16 50 40 A1 on on on on off on 8 70 0 3 1 1 1 1 1 1 1 1 1 40 24 40 0 C 16 50 ...

Page 9: ...inutes day month year Relay 3 configuration s3 S4_S5 weighting for Tact of day 100 S4 S5 0 S3 Tset s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 50 A1 on on on off off on 8 70 0 3 1 1 1 1 1 1 1 1 1 50 24 50 0 C ...

Page 10: ...S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 0 A1 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 24 0 0 C 16 50 0 A2 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 16 50 0 A1 on on off off off...

Page 11: ... d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 0 A1 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 24 0 0 C 16 50 0 A2 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 5 5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 8 100 0 100 1 C 9 1 0 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 8 0 4 0 0 C 16 50 0 A1 on on off off off on 10 40...

Page 12: ... r5 16 50 0 A1 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 25 0 0 C 16 50 0 A2 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 27 0 0 C 5 5 100 A3 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 8 100 0 100 1 C 9 1 0 A4 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 8 0 4 0 0 C 16 50 0 A1 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 16 50 0 A2 on on off off off on 10 40 10 10...

Page 13: ...set s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 16 50 0 A1 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 24 0 0 C 16 50 0 A2 on on on on off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 5 5 100 A3 on on on on of...

Page 14: ...17 r4 r5 16 50 0 A1 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 25 0 0 C 16 50 0 A2 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 27 0 0 C 16 50 0 A1 on on on off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 25 0 0 C 16 50 0 A2 on on on off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 27 0 0 C 5 5 100 A3 on on on off off off 8 70 0 3 0 1 1 1 1 1 1 1 8 100 0 100 1 C 16 50 0 A1 on on off off off...

Page 15: ...n on on off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 16 50 0 A2 on on on off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 28 0 0 C 5 5 100 A3 on on on off off off 8 70 0 3 0 1 1 1 1 1 1 1 8 100 0 100 1 C 16 50 0 A1 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 24 0 0 C 16 50 0 A2 on on off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 26 0 0 C 16 50 0 A1 on on on off off on 10 40 10 10 1 1 1 ...

Page 16: ...or Tact of day 100 S4 S5 0 S3 Tset s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 ATHEN 175 XL AD VS ALU NORMA 232139 A1 16 50 0 A1 on off off off off on 10 40 10 10 1 1 1 1 1 1 1 1 8 0 25 0 0 C 16 50 0 A1 on off on of...

Page 17: ...nable A5 Allow local display to start defrost Defrost Stop Temperatur Max defrost Time Drain postheating time Drain preheating tmie Number of Defrost day Sunday day Monday day Tuesday day Wednesday day thurstay day Friday day Saturday hour minutes day month year Relay 3 configuration s3 S4_S5 weighting for Tact of day 100 S4 S5 0 S3 Tset s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset ...

Page 18: ...ratur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 o17 r4 r5 Athen 207 210 XL S VS 224505 A3 5 5 100 A3 off off on off off off 8 70 0 3 0 1 1 1 1 1 1 1 1 100 0 100 1 C 16 50 0 A1 on on on on off off 8 70 0 3 0 1 1 1 1 1 1 1 1 0 24 0 0 C 16 50 0 A2 on on on on off off 8 70 0 3 0 ...

Page 19: ...y day Monday day Tuesday day Wednesday day thurstay day Friday day Saturday hour minutes day month year Relay 3 configuration s3 S4_S5 weighting for Tact of day 100 S4 S5 0 S3 Tset s3 S4_S5 weighting f 100 S4 0 S3 S3 S4_S5 temperatur offset Temperatur unit C F Cabinet Typ Part Number A13 A14 A36 P10 P1 P2 P3 P4 P5 d61 d02 d04 d20 d40 d90 d71 d72 d73 d74 d75 d76 d77 t07 t08 t45 t46 t47 L03 r15 r01 ...

Page 20: ...the man defrost key in order get to the parameter value This should then be changed using the key up or standby reset down To store the set value the man defrost key must be pressed Following this you return to the set parameter 4th step To store the bus address press the man defrost key once to quit the address menu and get back to the current temperature 7th step If you are in the main menu you ...

Page 21: ...124 at 5 1 2 page 8 Add new Setup 232139 232252 232264 and 232268 at 5 2 2 page 15 Add new Setup 232266 at 5 2 3 page 16 WI 550 4 22 10 2012 M Horn Add new Setup 232272 at 5 1 2 page 8 Add new Setup 232108 at 5 2 1 page 9 WI 550 5 23 10 2012 M Horn Add new Setup 233463 at 5 1 2 page 8 WI 550 6 29 10 2012 M Horn Change Parameter r01 from 27 to 29 for A1 and from 29 to 31 for A2 and Parameter r4 for...