Installing the head 
 

 

Align the components as show in the Figure. 

 

Mate the detector head 1nto the base and twist clockwise to secure it. 

 

In  case  that  detector  head  is  not  matching  marks  with  the  base  the 
detector will operate but connection polarity of remote LED annunciator 
are changed and then it is not assured its well performed operation.  

 

The maximum number of detector installed in the same loop is 30 units. 

 

After all detector have been installed apply power supply to the loop.

 

 
CAUTIONS. 

 

 

To prevent detector from dirty effect and warranty cancellation, detector 
must remain covered until the area is clean and dust free. 

 

Detector protection cover is not intended to provide complete protection 
against  dust  ambient  pollution,  therefore  detector  should  be  removed 
before  beginning  to  made  masonry  works,  inner  space  revamping  or 
other dust producing activity. 

 

Do not paint any part of detector because paint can close entry holes and then detector operation will be affected.  

 

Detector protection cover must be removed before fire detection system can be made operational. 

 

TESTING. 

 
Detectors must be tested after installation and following periodic maintenance. 
 
Before  testing,  notify  to  the  proper  authorities  that  the  heat  detector  system  is  undergoing  maintenance,  and  be  sure  that  all  required  functions 
related to alarm emergency exit, extinguishing system and automatic extinguishing shoot in are cancelled.  
  

 

Check that when you remove each detector from the base the fire alarm panel will be move announcing zone fault notice. If no  any fault is 
coming then recheck that there are not placed 2 wires or more at the same detectors base clamp at the terminal block.      

 

Check to see if the indicator red LED is flashing every 4~6 seconds. If red LED fails to flash, it indicates the detector non-operation condition 
or a faulty wiring is made.  

 

Magnet testing: 

 

Position  the  Test  Magnet  against  the  side  of  the  detector  housing  marked  “TEST”  for  at  least  10  seconds.  The  detector  will 
generate an alarm signal being recognized externally by a continuous lighting from two external LED and fire alarm panel shall be 
in alarm mode. 

Heat sensor testing: 

 

Subject the detector to a flow of warm air at a temperature of between 65ºC and 80ºC from a distance of several centimetres. The 
detector should alarm within 30 seconds. 

 

If a remote LED  annunciator is  coupled then also shall  be light  activated.  If lighting  activation  does not  arrive checking for  wiring and  well 
done detector plug-in into base is required to be done it again 

 

To  make  same  detector  testing  as  above  mentioned  for  another  selected  detector  placed  at  the  same  detection  loop,  first  at  all  you  shall 
reset the loop by switching-off from the remote fire alarm panel and also check the zone is in stand-by mode before start-up  with the next 
one detector checking.     

 
All detectors not capable to perform testing as above indicated must be replaced for technical service attendance. 
 
After testing implementation the alarm emergency exit, extinguishing system and automatic extinguishing shoot in functions cancelled previously 
at the fire alarm panel shall be activate and proper authorities shall be informed that the fire alarm system is again in operation. 

 
DETECTOR MAINTENANCE GUIDELINE. 

 
The recommended minimum requirement for detector maintenance consists of an annual cleaning of dust from the detector head using a vacuum 
cleaner.  All ambient head detector entry holes shall be keeping totally cleaned from ambient entry obstacles. For an exhaustive clean treatment 
the detector head should be send to AGUILERA ELECTRONICA, Customer Assistance Department.   
 
Do not attempt to disassemble factory sealed detector head. Opening the detector head the detector warranty will be void. 
 

SPECIFICATION. 

 
Power Supply 

 

 

15 ~ 35 VDC 

Standby current: 

 

 

35 µA 

Alarm current: 

 

 

70 mA max. 

Loop Wires sizes: 

 

 

2 X 1.5 mm

Operating Temperature Range: 

 

0º C a +50º C ambient dry temperature. 

Operating Humidity Range: 

 

10% al 90% Relative Humidity, Non-condensing. 

Start-up Time (Max.):   

 

60 s 

Lighting Annunciators:  

 

Standby:   

Leds flashing once every 4~6 seconds. 

Alarm: 

 

Continuous red lighting from LEDs 

Remote alarm output, rate: 

 

Remote LED annunciator, 6 VDC 

Detector Dimensions:   

 

Cover : 99 mm. (Diameter) 

Cover Height with base: 46 mm. 

Raw Material: 

 

 

White ABS plastic.

 

1º ALING WITH SHORT MARK
    AND PLACE THE DETECTOR 
    INTO THE BASE

2º TWIST CLOCKWISE 
    TO ALIGN WITH TWO 
    LONG MARKS

BASE DETECTOR

HEAD DETECTOR

EN 54-5:2000

 2831

05

2831-CPR-F4556