aguilera electronica AE/C5-TV Installation Manuallines Download Page 1

 
 

Ae-man-322-0.0 v1.3 

 

 

 

 

 

 

 

                             TECHNICAL MANUAL 

 

HEADQUARTER OFFICE & FACTORY

:  C/ Julián Camarillo, 26 28037 

– MADRID  (SPAIN) 

Phone.:+34 91 754 55 11   

www.aguilera.es

 

 

 

HEAT DETECTOR MOD.: AE/C5-TV 
 

The  AE/C5-TV  model  is  a  rate  of  rise  with  fixed  temperature  detector.  It  provides  an  ambient  temperature  surveillance  based  on  two  operation 
levels as follow: 
 

 

Rate or Rise: In case of the ambient temperature increase sharply more than a prefixed value during a selected period of time the detector 
will generate an alarm. 

 

Fixed: When the ambient temperature is increasing slowly higher than a prefixed value, the detector will generate an alarm.  

 
Each detector has two LEDs located in opposite side at the external assembly cover to inform to users by flashing about if the detector is in stand-
by operation or in permanent alarm as well. Remote LED annunciator capability is available upon request as an optional accessory to be wired to 
the detector base terminals block. 
 
This  detector  have  a  latching  alarm  feature.  In  case  the  detector  in  alarm  function  to  move  it  to  stand-by  operation  is  requested  to  produce  a 
detector power supply switch-off from the remote fire alarm panel. 
 
This detector model is manufactured and certified according to EN 54-7:2000 standard.  Class A2R heat detector. 

 

A  heat  detector  will  respond  only  when  a  fire  is  well  established  and  generating  a  high  heat  output  or  where  the  environment  is  dirty  or  smoky 
under normal conditions.  

 

INSTALLATION GUIDELINES. 

 

Mounting 

 

The  fixed  base  detector  should  be  mounted  directly  onto  an  electrical  junction  box  such  as  an  octagonal  (75mm,  90mm  or  100mm),  a  round 
(75mm) or a square (100mm) box without using any type of mechanical adapter. 

 

Detectors loop wiring 

 

Switch-off power supply to the 

detector’s fixed base before plug-in any detector main frame to the fixed base.  

 

 

Positive  wire  from  detection  loop  shall  be  connected  to  the  block  terminal  marked  as  2  (loop  input).  The  terminal  block  has  double  and 
separate terminals marked as 2, one for loop input and the other one as loop output. 

 

Negative  wire  from  detection  loop  shall  be  connected  to  the  block  terminal  marked  as  5.  The  terminal  block  has  double  and  separate 
terminals marked as 5, one for loop input and the other one as loop output. 

 

To built-up  the detection loop to the next one detector or to the end of line proceed connecting by wire the  free position 2 at the  terminal 
block with the position 2 (loop input) at  the n

ext one detector’s block terminal or to the end of line.  This procedure allows detection loop as 

an open line operation type. 

 

Proceed with negative wire in the same way as before mentioned for terminal block marked as 5. 

 

In case it is required to install a remote LED annunciator, connections from annunciator will be made between its positive to terminal block 6 
and negative to terminal block 3 at the base detector.   

 
 

 

 

 

Reviews: