Installing the head 
 

 

Align the components as show in the Figure. 

 

Mate the detector head into the base and twist clockwise to secure it. 

 

In case that detector head is not matching marks with the base the 
detector will operate but connection polarity of remote LED annunciator 
are changed and then it is not assured its well perfomed operation.  

 

The maximum number of detectors installed in the same loop is 30 units. 

 

After all detector have been installed apply power supply to the detector 
loop.

 

 

CAUTIONS. 

 

 

To prevent detector from dirty effect and warranty cancellation, the 
smoke detector must remain covered until the area is clean and dust 
free. 

 

Detector protection cover is not intended to provide complete protection 
against dust ambient pollution, therefore detector should be removed 
before beginning to made masonry works, inner space revamping or 
other dust producing activity. 

 

Do not paint any part of detector because paint can close air entry holes and then detector operation will be affected.  

 

Detector protection cover must be removed before fire detection system can be made operational. 

 

TESTING. 

 
Detectors must be tested after installation and following periodic maintenance. 
 
Before testing, notify to the proper authorities that the detector system is undergoing maintenance, and be sure that all required functions related 
to alarm emergency exit, extinguishing system and automatic extinguishing shoot in are cancelled.  
  

 

Check that when you remove each detector from the base the fire alarm panel will be move announcing zone fault notice. If no any fault is 
coming then recheck that there are not placed 2 wires or more at the same detectors base clamp at the terminal block.      

 

Check to see if the indicator green LED is flashing every 3~5 seconds. If green LED fails to flash, it indicates the detector non-foperation 
condition or a faulty wiring is made.  

 

Apply some smoke sample  from a test smoke aerosol to each detector during  at least 10 seconds to activate the detector-sensing 
chamber. When sufficient smoke portion has entry within the chamber then detector will generate an alarm signal  being recognized 
externally by a continuous lighting from two external LEDs and fire alarm panel shall be in alarm mode. 

 

If a remote LED annunciator is coupled  then also shall be light activated. If lighting activation does not arrive checking for wiring and well 
done detector plug-in into base is required to be done it again 

 

To made same detector testing as above mentioned for another selected detector placed at the same detection loop, first at all you shall 
reset the loop by switching-off from the remote fire alarm panel and also chek the zone is in stand-by mode before start-up with the next one 
detector checking.     

 
All detectors not capables to perform testing as above indicated must be replaced for technical service attendance. 
 
After testing implementation the alarm emergency exit, extinguishing system and automatic extinguishing shoot in functions cancelled previously 
at the fire alarm panel shall be activate and proper authorities shall be informed that the fire alarm system is again in operation. 

 
DETECTOR MAINTENANCE GUIDELINE. 

 
The recommended minimum requirement for detector maintenance consists of an annual cleaning of dust from the detector head using a vacuum 
cleaner.  All ambient head detector entry holes shall be keeping totally cleaned from ambient entry obstacles. For an exhaustive clean traitment 
the detector head should be send to AGUILERA ELECTRONICA, Customer Assistance Department.   
 
Do not attempt to disassemble factory sealed detector head. Opening the detector head the detector warranty will be void. 
 

SPECIFICATION. 

 
DC:PowerSupply 

 

 

15 ~ 35 Vdc 

Standby 

current: 

  35 

µA 

Alarm 

current: 

  70 

mA 

max. 

Loop Wires sizes: 

 

 

2 X 1.5 mm

Operating Temperature Range:   

10ºC a +50º C ambient dry  temperature. 

Operating Humidity Range: 

 

10% al 90%  Relative Humidity, Non-condensing. 

Start-up Time (Max.):   

 

60 s 

Lighting Annunciators:  

 

Standby:  Leds flashing once every 3~5 seconds. 
Alarm: 

Continuous red lighting from LEDs 

Remote alarm output, rate: 

 

Remote LED annunciator, 6 Vdc. 

Detector 

Dimensions: 

  Cover 

 

  99 

mm. 

(Diameter) 

Cover Height with base:  

46 mm. 

Raw 

Material: 

  White 

ABS 

plastic. 

 

1º ALING WITH SHORT MARK

    AND PLACE THE DETECTOR 
    INTO THE BASE

2º TWIST CLOCKWISE 

    TO ALIGN WITH TWO 
    LONG MARKS

BASE DETECTOR

HEAD DETECTOR

EN 54-7:2000

LPCB Nº 512a/02

          0832

      0832-CPD-0203