Installation & Operation Manual Merlin GDP2X
AGSGDP2X - IOM Iss: 3 03-20
12
Alarm Messages
The GDP2X will display messages when in alarm – the messages are prompted from external
devices that have been connected i.e. heat sensor or remote emergency stop.
When the GDP2X goes in to alarm, the user can silence the audible buzzer by pressing MUTE.
During the alarm, the gas will be shut off and no gas detection details will be available.
After the cause of alarm has been rectified – press the RESET button on the GDP2X panel.
Alarm Message List
EMERGENCY SHUT OFF
An emergency shut-off button has been activated.
Pressing MUTE on the GDP2X will silence the audible alarm buzzer.
Investigate and rectify the issue before RESETTING the panel.
FIRE PANEL ALARM
The fire alarm panel has reached alarm status.
Pressing MUTE on the GDP2X will silence the audible alarm buzzer.
Investigate and rectify the issue before RESETTING the panel.
HEAT SENSOR ALARM
Heat sensor/ thermal link has reached alarm status.
Pressing MUTE on the GDP2X will silence the audible alarm buzzer.
Investigate and rectify the issue before RESETTING the panel.
DETECTOR ALARM
If dangerous gas levels are detected, your GDP2X will
show the detector ID in alarm in the top left hand
corner.
Pressing MUTE on the GDP2X will silence the audible alarm buzzer.
Investigate and rectify the issue before RESETTING the panel.
The cause of alarm will have to be investigated and rectified before resetting the GDP2X.