AGS CO2-X Installation Operation & Maintenance Download Page 10

Installation, Operation & Maintenance                                                                                   Merlin CO2-X

 

 

 

Rev 5   10-21 

10  

   End of Operational Life (EOL) 

 
This message indicates that the CO2-X monitor has reached its expected operational lifecycle.  
No gas or temperature levels will be displayed. The expected lifetime is 10 years.  
 

 
Contact your supplier and replace the unit immediately. 
The expected lifecycle of 10 years may vary depending on environmental conditions. 

 
 

General Maintenance

 

   Cleaning 

 

Keep your detector in good working order follow these basic principles; 
 

 

Carefully remove any accumulated dust from the outer enclosure using a slightly damp cloth. 

 

Never use detergents or solvents to clean your device – this may permenantly or temporarily damage the gas 
sensing elements. 

 

Never spray air fresheners, hair spray, paint or other aerosols near the device. 

 

Never paint the device. Paint will seal vents and interfere with the device. 

 

 

 

High concentrations of alcohol found in many products may damage, deteriorate or affect the gas sensing 
elements – such as; wine; deodorants; stain removers; thinners etc. 

 

   Auto-Calibration 

 

Our CO

2

 sensors are designed to automatically recalibrate using background CO

2

 levels ±100ppm. 

For maintenance purposes, the device should be exposed to fresh air intermittently to aid with this process. 
Inaccuracies that do not resolve over a 24 hour period may require temporary removal of the device, from site, for an 
extended exposure to fresh air. 
 

   Testing your CO2-X 

 
The aim of the test is to make sure the CO2-X is working at its optimum by briefly exposing a level of carbon dioxide 
to send the device into an alarm state ensuring all system outputs/relays activate then it is working safely.  
If the system fails to operate as intended in an alarm state, the device must not be used until a full inspection and 
service has been conducted.  
 
To do this, simply breathe near or into the device. To increase reaction time, cover the escape vents. 
If in doubt, contact your supplier. 

 

 

 

 
 
 
 
 
 
 

Summary of Contents for CO2-X

Page 1: ...cally switch between ventilation programs when gas is used Boost Mute and Wake Up feature Installation Operation Maintenance Please read this manual carefully and retain for future use The Merlin CO2...

Page 2: ...ounting 4 Board Overview 4 Wiring your CO2 X 5 Configuration Settings 6 Configuration 6 Factory Set Condition 7 Operation 8 Initial Power Up Indicators 8 Traffic Light Indicator 9 Alarms Configuration...

Page 3: ...d to replacement of the product with repaired product at the discretion of the manufacturer This warranty is void if the product has been damaged by accident unreasonable use neglect tampering or othe...

Page 4: ...ere possible monitors must be fixed in such a position as to allow natural air circulation These recommended heights may vary based on airflow and temperature conditions in addition to the proposed ap...

Page 5: ...until the gas supply is turned off see Settings for configuration Recommended for teaching areas with gas appliances such as laboratories and food technology rooms CO2 ALARM Not a mains output This t...

Page 6: ...setting red Press to save desired setting Configuration NAT Natural Ventilation Mode Recommended for buildings without mechanical ventilation Pre Alarm 1300ppm 23 C 73 4 F Alarm 1500ppm 25 C 77 0 F C...

Page 7: ...minutes Boost can be activated only if analogue outputs are set to either CO2 or DUAL mode only Select 1 2 3 4 5 6 7 8 9 10 minute s FAN ENABLE Fan switch is energised by CO2 ON 600ppm OFF 550ppm TEMP...

Page 8: ...rs when the touch button f is pressed The audible alarm buzzer must be set to on or every 10 minutes and can only occur when gas is in use or KITCH Ventilation mode is selected and when CO2 levels ris...

Page 9: ...Default Green 1500ppm 23 C 73 4 F Yellow 1500ppm 23 C 73 4 F Red 2800ppm 25 C 77 0 F CO2 Pre alarm relay switch 2800ppm CO2 Alarm relay switch 4500ppm 0 10V Analogue Output Progression Min output 1 5V...

Page 10: ...e device High concentrations of alcohol found in many products may damage deteriorate or affect the gas sensing elements such as wine deodorants stain removers thinners etc Auto Calibration Our CO2 se...

Page 11: ...mm 5 51 x 3 74 x 1 18 Unit Weight Approx 0 08kg Housing Material Polylac PA765 Environmental Ingress Protection IP40 Storage Conditions Dry Temp 10 50 C 14 122 F 30 80 rh Compliance CE EN 50270 EN 610...

Page 12: ...this document or their consequences AGS would greatly appreciate being informed of any errors or omissions that may be found in the content of this document For information not covered in this documen...

Reviews: