![Agilent Technologies Varian MERCURY Series Installation Planning Download Page 23](http://html1.mh-extra.com/html/agilent-technologies/varian-mercury-series/varian-mercury-series_installation-planning_2868233023.webp)
01-999021-00 A0100
Installation Planning Guide
23
Chapter 3.
Site Preparation
Sections in this chapter:
•
3.1 “Line Voltage Variation” next
•
3.2 “Uninterrupted Power Supply (UPS)” page 24
•
3.3 “Electrical Outlets” page 24
•
3.4 “Compressed Air Supply” page 25
•
3.5 “Compressed Nitrogen Gas” page 26
•
3.6 “Telephone and Internet Access” page 26
•
3.7 “Air Conditioning” page 26
•
3.8 “Computer Preparation” page 27
Before designing the room layout, verify the configuration with a Varian representative.
Site preparation must conform with national and local codes, which take precedence over
any recommendations in this guide. Approval by a building inspector may be necessary.
3.1 Line Voltage Variation
Measure and record the ac line voltage for 48 hours using a suitable power line analyzer
such as the BMI model 4800 power line disturbance analyzer. Provide a copy for the Varian
installation engineer. Requirements are the following:
•
Long-term voltage variations (slow average) do not exceed 8% of nominal line tap
voltages (117
±
15 Vac).
•
Short-term voltage variations (sag or surge), with a duration between several
milliseconds and several seconds, do not exceed 10% of nominal line tap voltage (117
±
15 Vac).
•
Line transients (impulse) with a duration between 1
µ
s and 800
µ
s, not to exceed 50 V
peak above or below nominal line tap voltage (117
±
15 Vac). These transients must be
measured at the power plug with a load connected that simulates the spectrometer load.
•
AC line frequency does not vary by more than +0.5 to –1.0 Hz.
The purchase of a line conditioner and regulator is strongly recommended. By providing
protection against transients and improving line regulation, total system “up-time” will
improve and the electronic components within the system will last longer. In many
locations, a good power conditioning system will pay for itself within a few years. Contact
a local power consultant for suitable equipment in your area.
In areas where the primary line voltage is not 117 Vac, a user-supplied step-down isolation
transformer of sufficient capacity (2.0 kW) is required. A suitable isolation transformer is
available from Varian.