Model 5500 COLLECT

an

DRAIN

®

 Owner’s Manual

4

INSTALLATION INSTRUCTIONS

Unpacking:

1.  Unpack the COLLECT

an

DRAIN

® 

M5500 unit and carefully inspect for any 

shipping damage.

2.  Verify box contents:

•  COLLECT

an

DRAIN

® 

M5500 unit

•  Four (4) Rubber Mounting Washers
•  Two (2) Door Keys
•  Electrical Wiring Schematic
•  M5500 System Drawing

Sprinkler System Preparation:

If installing in a new system, proceed to Mounting Instructions below, otherwise 
continue with Preparation Instructions.
If adding additional installations, see NFPA 13, and NFPA 25.

1.  Isolate the zone where the COLLECT

an

DRAIN

®

 will be installed.

2.  Relieve air pressure from the branch line.
3.  Remove the existing auxiliary drain.

Mounting:

Use the four mounting tabs (3/8” holes x 4) to install the M5500 to a wall or other 
secure structure. If wall is uneven use bushings or stand-offs to prevent cabinet 
from bending when mounted.

1.  Place the rubber washers behind the mounting 

tabs to hold the M5500 off of the wall. Select 
fasteners suitable for attachment and capable 
of supporting the 56 lb. weight of the M5500.

2.  Connect to the 1” NPT supply pipe in accor-

dance with NFPA 13 in regards to low-point 
drain installations.

3.  Connect the 1” NPT drain pipe to suitable drain 

plumbing for which the discharge is into or near 
a drain. The use of an air gap is recommended.

Summary of Contents for COLLECT anDRAIN 5500

Page 1: ...1 Model 5500 Owner s Manual INST 5500 8 20 AGF Manufacturing Inc...

Page 2: ...f typical collectors The Model 5500 maintains a comfortable temperature above freezing while minimizing power consumption AGF Manufacturing Inc 100 Quaker Lane Malvern PA 19355 www agfmfg com AGF Manu...

Page 3: ...mp Flash Test Reset button for one 1 second Reset System Test Reset button for five 5 seconds will reboot the system and return to collect state Drain Override Drain and Test Reset buttons simultaneou...

Page 4: ...OLLECTanDRAIN will be installed 2 Relieve air pressure from the branch line 3 Remove the existing auxiliary drain Mounting Use the four mounting tabs 3 8 holes x 4 to install the M5500 to a wall or ot...

Page 5: ...l enclosure Refer to the electrical schematic as necessary 5 Connect the 120V AC hot wire to the top of the circuit breaker 6 Connect the 120V AC neutral wire to one of the neutral N terminals 7 Conne...

Page 6: ...set the red thermostat set point dial to the factory default setting of 50 F NOTE It is the owner s responsibility to set the thermostat based upon the climate conditions of the installed location The...

Page 7: ...e local drain button is pressed or if it has been wired the remote button is pressed While the alarm is active an auxiliary contact is also triggered and is capable of being wired back to a central co...

Page 8: ...ity installation location and exposure to sunlight The following graph shows an estimation of the daily energy consumption verses the ambient temperature when the set point is 50 F The M5500 features...

Page 9: ...n cycle the PLC senses a malfunction such as the valves not fully actuating or the condensate not draining from the system the system alarm will stay on or enter the alarm state Refer to the Quick Ref...

Page 10: ...n condensation from the system or conduct regularly scheduled testing and maintenance could result in system failure due to freezing System must be maintained per NFPA 25 It is especially important th...

Page 11: ...oor of the M5500 electrical enclosure 3 Turn the red Thermostat Set Point Dial clockwise or counterclockwise to the desired setting 4 Take note of the new thermostat set point Thermostat Set Point ___...

Page 12: ...AGF Manufacturing Inc 100 Quaker Lane Malvern PA 19355 Phone 610 240 4900 Fax 610 240 4906 www agfmfg com...