11
OSA 3
Seperator alarm OSA 3 • Manual
Note:
For the oil/petrol/grease warn-
ing device to trigger an alarm, a
marked layer must form between
the water and the oil/grease/pet-
rol. The equipment will not work in
an emulsion or where grease or oil
has been dissolved by chemicals
Operation on startup
The following buttons can be found on the
unit: = arrow left, = arrow right, =
arrow down and reset to reset.
• The
“ ”
and
“ ”
buttons are used to
increase and decrease input values in
the display
• “ ” down is used to acknowledge the
input values and to move forwards
through input menus
Backlight in display:
Flashes when an alarm or an error message
has been triggered. Use the reset button to
acknowledge alarms.
Buzzer:
A built-in buzzer makes a noise when
an alarm or an error message has been
triggered. The buzzer sound is repeated
automatically after 20 hours if R1 is not set
for an acknowledgeable function.
Checks when starting the electronic unit
Check that all connections and installation
are completed correctly before connecting
to a power supply.
• Switch on the power supply to the elec-
tronic unit
This screen is displayed for approx. 15
seconds, after which the current program
version can be viewed on screen.
The automatic setup function then com-
mences. The first step involves setting the
date and time, then the unit carries out a
check of sensor inputs on startup and reg-
isters automatically connected sensors
• Set date/time
Use the arrow keys on the electronic unit
to move the cursor and set the date and
time. The key moves from the first digit
in the date and forwards every time it is
pressed. To reduce a value, press , and
to increase a value, press . When you
have finished, hold down for 3 sec and
the unit will switch to scanning sensors.
Commissioning
Automatic Setup
SEPARATOR ALARM
STATUS OK
ver 1.03
<,> = INCREASE/DECREASE
v = NEXT
v (3 sec) = DONE
2012.01.01 00:00