Mounting and commissioning
26
ProCalida® GT 3
5.7
Adjusting the control valves
With flow meter
1.
Fully open the flow valve (
V1
). Open the return valve (
R1
) until
the calculated flow rate (
W
) is indicated at the flow meter (
D
).
2.
Pull the ring to the front to unlock.
3.
Turn the ring all the way to the mechanical stop of the flow
valve.
4.
Push the ring back to lock.
5.
Turn the thermometer (optional) into reading position (see chap-
ter 5.8, page 28).
6.
Repeat the steps for all other heating circuits
7.
Fit the protective cover.