Mounting and commissioning
24
LAG-14 ER
6.5
Mounting the test valve
The LAG mounting kit from AFRISO contains a test valve with 1" fe-
male thread and a hose connection piece for 12 x 2 mm hoses as
well as all other connection parts required for installing the leak de-
tector.
The test vale should be mounted to the connection point opposing
connection point of the black LAG container.
Mount the test valve at least 100 mm below the bottom edge of the
LAG fluid container at the tank.
There must be sufficient space below the test valve for a container to
collect leak detection fluid escaping during the function test.
The leak detection fluid must escape at the test valve with a flow rate
of approx. 0.5 l/min during the function test.
6.6
Mounting the control unit
Fig. 7: Control unit with mounting frame for panel mounting; right:
control panel cut out
Do not install the control unit in hazardous areas (EX areas).
Mount the control unit to an even, rigid and dry wall at eye level.
The control unit must be accessible and visible at all times.
The control unit must not be exposed to water or splash water.
The control unit must not be installed in humid rooms.
The permissible ambient temperature at the control unit must
not be exceeded, see table 2, page 15.
Protect the control unit from direct atmospheric influences if it is
installed outdoors.