Technical data
LAG-14 ER
15
Table 2: Technical specifications control unit SE2
Parameter
Value
General specifications
Dimensions housing
(W x H x D)
100 x 188 x 65 mm
Weight
0.4 kg
Equipment group
(2014/34/EU)
Category (2014/34/EU)
Type of protection
Protection class
Supply voltage
Safety-related maximum
voltage U
m
Degree of protection
II
(1) G
[Ex ia] IIC
II
230 V, 50 Hz
253 V
IP 30
Response delay
< 1 second
Additional connections
1 output relay (1 changeover contact)
Breaking capacity output
relay
Max. 250 V. 2 A, resistive load
Relay fuse
T 2 A
Emissions
The A-weighted sound level of the au-
dible alarm is at least 70 dB(A) at a
distance of one metre
Operating temperature range
Ambient
-20 °C to +50 °C
Supply voltage
Nominal voltage
AC 230 V ± 10 %, 50/60 Hz
Nominal power
5 VA
Mains fuse
T 100 mA H (1.5 kA)
Electrical safety
Protection class
II (EN 60730-1)
Degree of protection
IP 30 (EN 60529)