Mounting and commissioning
14
Europress
The leak detector must not be installed in hazardous areas or in
access chambers of underground tanks.
If the case of outdoor applications, the leak detector must be
mounted in a protective housing with IP 55 protection. If the leak
detector is installed in a protective housing, an additional
weather-proof audible alarm must be installed outside of the
protective housing. See chapter 11, page 31 for accessories.
If the leak detector is installed below rooftops or in rooms that
are only partially closed, protect it against direct atmospheric in-
fluences or use a protective housing as mentioned above.
6.3
Installing the leak detector
1.
Fasten the leak detector the wall (use
A
or
B
),
a drilling template is included.
2.
Open the leak detector.
3.
Connect the unit electrically as described in chapter 6.4 on
page 15.